Modbus Read, Write and Override Parameters plus Exception Codes

 

Parameter

Register

Data

Access

 

 

Data Range or

 

Description

Address

Type

 

 

 

Enumerated Selection

 

 

 

 

 

 

 

 

 

 

 

Hex

Decimal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lockout

0084

132

INT

R/W

 

0 = No Lockout

 

(keyboard only)

 

 

 

 

1

= Calibration Locked out

 

Changes to data are

 

 

 

 

2

= +Configuration – Timer,

 

 

 

 

 

 

 

Tuning, SP Ramp,

 

always possible via

 

 

 

 

 

 

 

 

 

 

 

 

 

Accutune are read/write

 

communications

 

 

 

 

3

 

regardless of this

 

 

 

 

= +View – Tuning and SP

 

configuration.

 

 

 

 

 

 

Ramp are read/write, no

 

 

 

 

 

 

 

 

other parameters are

 

 

 

 

 

 

 

 

available

 

 

 

 

 

 

4

= Maximum Lockout

 

 

 

 

 

 

 

 

 

Security Code

0050

080

INT

R/W

 

0 to 9999

 

 

 

 

 

 

 

 

 

Man/Auto Key

00BF

191

INT

R/W

 

0 = Disable

 

Lockout

 

 

 

 

1

=Enable

 

 

 

 

 

 

 

 

 

Run/Hold Key

00EE

238

INT

R/W

 

0 = Disable

 

Lockout

 

 

 

 

1

=Enable

 

 

 

 

 

 

 

 

 

Setpoint Key

00ED

237

INT

R/W

 

0 = Disable

 

Lockout

 

 

 

 

1

=Enable

 

 

 

 

 

 

 

 

 

NOTE 1: Writes to these locations are not available when Accutune is enabled.

4/07

UDC2500 Universal Digital Controller Product Manual

197

Page 211
Image 211
Honeywell UDC2500 manual Lockout 0084 132