Modbus RTU Function Codes

9.3 Function Code 20 (14h) - Read Configuration Reference Data

Description

Function code 20 (14 Hex) is used in this instrument to read information stored in its configuration database. Each configuration item is explicitly addressed by a file number and register address. IEEE 32-bit floating point and 16-bit integer formats are supported.

Request and Response Formats

The Request and Response formats for Function code 20 (14 Hex) are shown below. Details for each block reference follow.

Request Message Format

Slave

Address

Function

Byte

Reference

Code 14

Count

Type

 

 

 

 

 

 

File

Register

Register

Number

Address

Count

 

 

 

 

 

 

Reference

Type

File

Register

Register

Number

Address

Count

 

 

 

 

 

 

CRC Data

CRC Data

Response Message Format

Slave

Function

Byte

Data

Reference

Data

Data

Data

 

Byte

 

Address

Code 14

Count

Type

 

Count

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

Data

Byte

Count

Reference

Type

Data

Data

Data

Data

CRC Data

CRC Data

Byte Count

The Byte Count equals the number of bytes transmitted in either the request or response message and will be the minimum number required to transmit all requested data.

Data Byte Count

The Data Byte Count is the number of data bytes of the sub response including the Reference Type but not including itself. A floating point sub response has four bytes of data and one byte representing the reference type making the data byte count equal to five.