Modbus Read, Write and Override Parameters plus Exception Codes

10.7.6Input 1

Table 10-14lists all the register addresses and ranges or selections for the function parameters in Set-up Group Input 1.

 

 

Table 10-14 Set-up Group – Input 1

Parameter

Register

Data

Access

 

Data Range or

Description

Address

Type

 

 

Enumerated Selection

 

Hex

Decimal

 

 

 

 

 

 

 

 

 

 

 

Input 1 Type

00A8

168

INT

R/W

1 = B TC

 

 

 

 

 

2 = E TC H

 

 

 

 

 

3 = E TC L

 

 

 

 

 

4 = J TC H

 

 

 

 

 

5 = J TC M

 

 

 

 

 

6 = J TC L

 

 

 

 

 

7 = K TC H

 

 

 

 

 

8 = K TC M

 

 

 

 

 

9 = K TC L

 

 

 

 

 

10

= NNM H

 

 

 

 

 

11

= NNM L

 

 

 

 

 

12

= Nicrosil H TC

 

 

 

 

 

13

= Nicrosil L TC

 

 

 

 

 

14

= R TC

 

 

 

 

 

15

= S TC

 

 

 

 

 

16

= T TC H

 

 

 

 

 

17

= T TC L

 

 

 

 

 

18

= W TC H

 

 

 

 

 

19

= W TC L

 

 

 

 

 

20

= 100 PT RTD

 

 

 

 

 

21

= 100 PT LO RTD

 

 

 

 

 

22

= 200 PT RTD

 

 

 

 

 

23

= 500 PT RTD

 

 

 

 

 

24

= Radiamatic RH

 

 

 

 

 

25

= Radiamatic RI

 

 

 

 

 

26

= 0-20 mA

 

 

 

 

 

27

= 4-20 mA

 

 

 

 

 

28

= 0-10 mV

 

 

 

 

 

29

= 0-50 mV

 

 

 

 

 

30

= 100 mV

 

 

 

 

 

31

= 0-5 Vdc

 

 

 

 

 

32

= 1-5 Vdc

 

 

 

 

 

33

= 0-10 Vdc

 

 

 

 

 

34

= Unused

 

 

 

 

 

35

= Unused

 

 

 

 

 

36

= Thermocouple Differential

 

 

 

 

 

37

= PR40-PR20 Thermocouple

 

 

 

 

 

 

 

ATTENTION

Changing the Input Type will result in the loss of Field Calibration values and will restore the Factory Calibration values.

204

UDC2500 Universal Digital Controller Product Manual

4/07