Input Calibration
Step
Operation
Press
Result
3Calibrate 100 %
Function
You will see:
Upper Display = APLY ( 2 )
Lower Display = IN1SPN (10003)
4Check the Cold Junction Temperature
5Exit the Calibration Mode
Function
Function
then
Lower
Display
•Adjust your calibration device to an output signal equal to the 100 % range value for your particular input sensor. See Table
•Wait 15 seconds, and
If … | Then … |
you are calibrating a Thermocouple input | go to step 4 |
you are calibrating other than a | go to step 5 |
Thermocouple input |
|
The calculations for zero and span are now stored and you will see:
Upper Display = The cold junction temperature at the rear terminals
Lower Display = CJTEMP (10004)
The value in the upper display is in tenths of a degree. It is the current reading of the temperature as measured at the thermocouple terminals and recognized by the controller.
You can change this value, if it is in error, using the or
keys.
WARNING: The accuracy of the controller is directly affected by the accuracy of this value. It is recommended that this value not be changed under normal circumstances.
The controller stores the calibration constants and exits the calibration mode.
4/07 | UDC2500 Universal Digital Controller Product Manual | 145 |