Installation

COMMUNICATION MASTER

D+ (B) SHLD D– (A)

1 2

16 SHLD

SHLD

17 D+ (B)

D+

18 D– (A)

D–

TO OTHER

COMMUNICATION

CONTROLLERS

D– D+

120 OHMS

Connect shield to ground at one end only.

120 OHMS ON LAST LEG

1 Do not run the communications lines in the same conduit as AC power. 2 Use shielded twisted pair cables (Belden 9271 Twinax or equivalent).

Figure 2-15 RS-422/485 Communications Option Connections

COMMUNICATION MASTER

3

OR SWITCH

SHLD TXD– TXD+ RXD– RXD+

1

1414SHLDSHLD

1515RXDRXD+

16 RXD –

16 RXD-

1717TXDTXD+

2

1818TXDTXD–-

1Do not run the communications lines in the same conduit as AC power. Correct connections may require the use of an Ethernet cross-over cable.

2Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.

3Use Switch rather than Hub to maximize performance.

Figure 2-16 Ethernet Communications Option Connections

Figure 2-16 and Table 2-7shows how to connect a UDC to a MDI Compliant Hub or Switch utilizing a straight-through cable or for connecting a UDC to a PC utilizing a crossover cable.

4/07

UDC2500 Universal Digital Controller Product Manual

29

Page 43
Image 43
Honeywell UDC2500 manual 15 RS-422/485 Communications Option Connections