Monitoring and Operating the Controller

Configuration Check for Duplex

See Subsection 3.6 - Accutune Set Up Group for details.

Make sure:

TUNE has been enabled

DUPLEX has been configured to Manual, Automatic or Disabled

4.11.3Using AUTOMATIC TUNE at start-up for Duplex (Heat/Cool)

Used when DUPLEX has been configured for AUTOMATIC. This is the preferred selection for most Heat/Cool applications when tuning a new chamber. This selection will sequentially perform both Heat and Cool tuning without further operator intervention.

Table 4-12 Procedure for Using AUTOMATIC TUNE at Start-up for Duplex Control

Step

Operation

 

Press

Result

1

Configure LSP1

 

 

 

Until SP (Local Setpoint 1) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until LSP1 is a value within the

 

 

 

 

 

Heat Zone (output above 50%).

3

Configure LSP2

 

 

 

Until 2SP (Local Setpoint 2) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

4

 

 

or

 

Until LSP2 is a value within the

 

 

 

 

 

Cool Zone (output below 50%).

5

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

M-A

 

 

“Automatic” Mode

 

Reset

 

controllers with Manual option).

 

 

 

 

 

6

Show Tuning

 

 

 

Until “NoTUNE” is shown on lower

 

Lower

 

 

Prompt

 

Display

 

display.

 

 

 

 

 

7

Initiate Tuning

 

 

 

Select “DoSLOW” or “DoFAST” in

 

 

 

 

 

lower display.

 

Tuning in operation

 

 

 

Upper display will flash “TUNE” as

 

 

Lower

 

 

 

 

Display

 

long as ACCUTUNE process is

 

 

 

 

 

operating. When process

 

 

 

 

 

completes, tuning parameters are

 

 

 

 

 

calculated and lower display will

 

 

 

 

 

show “NoTune” prompt.

4.11.4Using BLENDED TUNE at start-up for Duplex (Heat/Cool)

When DUPLEX has been configured for DISABLE. This is the preferred selection for Heat/Cool applications which use a highly insulated chamber (a chamber which will lose heat very slowly unless a cooling device is applied). Only one local setpoint (LSP 1) is needed for this selection.

106

UDC2500 Universal Digital Controller Product Manual

4/07

Page 120