Honeywell UDC2500 manual Procedure #3, Troubleshooting Three Position Step Control Output Failure

Models: UDC2500

1 243
Download 243 pages 28.29 Kb
Page 181
Image 181

Troubleshooting/Service

Procedure #3

Table 7-7explains how to troubleshoot Position Proportional Output failure symptoms.

Table 7-7 Troubleshooting Three Position Step Control Output Failure

Step

What to do

How to do it

1

Make certain that the controller

Make Output Algorithm Set Up group function

 

is configured for Three Position

prompt OUT ALG = TPSC.

 

Step control.

Refer to Section 3.8.

 

 

2

Check the field wiring.

Refer to Section 2 - Installation for details.

3

Check the output.

Put the controller into Manual mode and

 

 

change the output from 0 % to 100 %.

4

Check whether the motor

Remove controller and short out Output 1 or

 

drives in both directions.

Output 2. The motor should go to either open

 

 

or closed. If it does controller is ok. If not,

 

 

repeat Step 1.

5

Check whether the motor

Refer to the motor instructions.

 

drives in either direction. If the

 

motor does not drive in either direction, check the motor. If the motor drives in one direction but not the other, go to Step 6

6Make sure the output relays are actuating properly.

7Change the two Output Relays or the Dual Relay Board (depending upon unit)

Put the controller into Manual mode. Vary the output above and below the present value. Observe “OT” in the Lower Display and the Relay Annunciators on the operator interface.

If they are not working properly, check the field wiring, then go to Step 5.

If they are, go to Step 7.

Installation instructions supplied with the new relays or board.

4/07

UDC2500 Universal Digital Controller Product Manual

167

Page 181
Image 181
Honeywell UDC2500 manual Procedure #3, Troubleshooting Three Position Step Control Output Failure, Refer to Section