Configuration

 

Function Prompt

 

Selection or Range of Setting

 

 

 

Parameter

 

Lower Display

 

Upper Display

 

 

 

Definition

 

English

Numeri

 

English

Numeric

 

 

 

 

 

 

 

c Code

 

 

Code

 

 

 

 

 

 

FINLSP

203

 

Enter a value within

 

 

 

SETPOINT RAMP FINAL SETPOINT

 

 

 

 

the setpoint limits

 

 

 

Enter the value desired for the final setpoint.

 

 

 

 

 

 

 

 

The controller will operate at the setpoint set

 

 

 

 

 

 

 

 

here when ramp is ended.

 

 

 

 

 

 

 

 

 

 

If the ramp is on HOLD, the

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

held setpoint

can be changed by the and

 

 

 

 

 

 

 

 

keys. However, the ramp time remaining and

 

 

 

 

 

 

 

 

original ramp rate is not changed. Therefore,

 

 

 

 

 

 

 

 

when returning to RUN mode, the setpoint

 

 

 

 

 

 

 

 

will ramp at the same rate as previous to the

 

 

 

 

 

 

 

 

local setpoint change and will stop if the final

 

 

 

 

 

 

 

 

setpoint is reached before the time expires. If

 

 

 

 

 

 

 

 

the time expires before the final setpoint is

 

 

 

 

 

 

 

 

reached, it will jump to the final setpoint.

 

 

 

 

 

 

 

 

 

SP RAMP and SP RATE will

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

cause the SP

portion of Accutune to abort.

 

 

 

 

 

 

 

 

PV Tune will continue to function normally.

 

 

 

 

 

 

 

 

Ramp is placed into HOLD while tuning

 

 

 

 

 

 

 

 

(TUNE configuration).

 

 

 

 

 

 

 

 

 

 

SPRATE

204

 

 

 

 

 

SETPOINT RATE—Lets you configure a

 

SP Rate

 

 

 

 

 

 

specific rate of change for any local setpoint

 

 

 

 

 

 

 

change.

 

operates only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when neither

 

 

DIS

0

 

 

DISABLE SETPOINT RATE—Disables the

 

SP Ramp or

 

 

 

 

 

 

setpoint rate option.

 

SP

 

 

ENAB

1

 

 

ENABLE SETPOINT RATE—Allows the SP

 

Programming

 

 

 

 

 

is running or

 

 

 

 

 

 

rate feature.

 

when SP

 

 

 

 

 

 

 

 

 

 

Ramp and SP

 

 

 

 

 

 

 

 

 

 

Programming

 

 

 

 

 

 

 

 

 

 

are disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EUHRUP

205

 

0 to 9999 in

 

 

 

RATE UP—Rate up value. When making a

 

 

 

 

Engineering units

 

 

 

setpoint change, this is the rate at which the

 

 

 

 

per hour

 

 

 

controller will change from the original

 

 

 

 

 

 

 

 

setpoint up to the new one. The ramping

 

 

 

 

 

 

 

 

(current) setpoint can be viewed as SPn in

 

 

 

 

 

 

 

 

the lower display.

 

 

 

 

 

 

 

 

Entering a 0 will imply an immediate change

 

 

 

 

 

 

 

 

in Setpoint (i.e., no rate applies).

 

 

 

 

 

 

 

 

 

 

 

40

UDC2500 Universal Digital Controller Product Manual

4/07

Page 54
Image 54