Configuration
| Function Prompt |
| Selection or Range of Setting |
|
|
| Parameter | |||
| Lower Display |
| Upper Display |
|
|
| Definition | |||
| English | Numeri |
| English | Numeric |
|
|
|
|
|
|
| c Code |
|
| Code |
|
|
|
|
|
| FINLSP | 203 |
| Enter a value within |
|
|
| SETPOINT RAMP FINAL SETPOINT— | ||
|
|
|
| the setpoint limits |
|
|
| Enter the value desired for the final setpoint. | ||
|
|
|
|
|
|
|
| The controller will operate at the setpoint set | ||
|
|
|
|
|
|
|
| here when ramp is ended. | ||
|
|
|
|
|
|
|
|
|
| If the ramp is on HOLD, the |
|
|
|
|
|
|
|
| ATTENTION | ||
|
|
|
|
|
|
|
| held setpoint | can be changed by the ▲ and ▼ | |
|
|
|
|
|
|
|
| keys. However, the ramp time remaining and | ||
|
|
|
|
|
|
|
| original ramp rate is not changed. Therefore, | ||
|
|
|
|
|
|
|
| when returning to RUN mode, the setpoint | ||
|
|
|
|
|
|
|
| will ramp at the same rate as previous to the | ||
|
|
|
|
|
|
|
| local setpoint change and will stop if the final | ||
|
|
|
|
|
|
|
| setpoint is reached before the time expires. If | ||
|
|
|
|
|
|
|
| the time expires before the final setpoint is | ||
|
|
|
|
|
|
|
| reached, it will jump to the final setpoint. | ||
|
|
|
|
|
|
|
|
| SP RAMP and SP RATE will | |
|
|
|
|
|
|
|
| ATTENTION | ||
|
|
|
|
|
|
|
| cause the SP | portion of Accutune to abort. | |
|
|
|
|
|
|
|
| PV Tune will continue to function normally. | ||
|
|
|
|
|
|
|
| Ramp is placed into HOLD while tuning | ||
|
|
|
|
|
|
|
| (TUNE configuration). | ||
|
|
|
|
|
|
|
|
| ||
| SPRATE | 204 |
|
|
|
|
| SETPOINT | ||
| SP Rate |
|
|
|
|
|
| specific rate of change for any local setpoint | ||
|
|
|
|
|
|
| change. | |||
| operates only |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
| when neither |
|
| DIS | 0 |
|
| DISABLE SETPOINT | ||
| SP Ramp or |
|
|
|
|
|
| setpoint rate option. | ||
| SP |
|
| ENAB | 1 |
|
| ENABLE SETPOINT | ||
| Programming |
|
|
|
| |||||
| is running or |
|
|
|
|
|
| rate feature. | ||
| when SP |
|
|
|
|
|
|
|
|
|
| Ramp and SP |
|
|
|
|
|
|
|
|
|
| Programming |
|
|
|
|
|
|
|
|
|
| are disabled |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| EUHRUP | 205 |
| 0 to 9999 in |
|
|
| RATE | ||
|
|
|
| Engineering units |
|
|
| setpoint change, this is the rate at which the | ||
|
|
|
| per hour |
|
|
| controller will change from the original | ||
|
|
|
|
|
|
|
| setpoint up to the new one. The ramping | ||
|
|
|
|
|
|
|
| (current) setpoint can be viewed as SPn in | ||
|
|
|
|
|
|
|
| the lower display. | ||
|
|
|
|
|
|
|
| Entering a 0 will imply an immediate change | ||
|
|
|
|
|
|
|
| in Setpoint (i.e., no rate applies). | ||
|
|
|
|
|
|
|
|
|
|
|
40 | UDC2500 Universal Digital Controller Product Manual | 4/07 |