Configuration

3.13 Communications Group

Introduction

The Communications group lets you configure the controller to be connected to a host computer via Modbus® or Ethernet TCP/IP protocol. Two parameters in this Group, Communications Station Address and TX Delay, are also used for IR communications. No other parameters affect IR communications.

Introduction

A controller with a communications option looks for messages from the host computer. If these messages are not received within the configured shed time, the controller will SHED from the communications link and return to stand-alone operation. You can also set the SHED output mode and setpoint recall, and communication units.

Up to 99 addresses can be configured over this link. The number of units that can be configured depends on the link length, with 31 being the maximum for short link lengths and 15 drops being the maximum at the maximum link length.

Function Prompts

Table 3-14 Communications Group (Numeric Code 1000) Function Prompts

Function Prompt

Selection or Range of

 

Parameter

Lower Display

Setting

 

Definition

 

 

Upper Display

 

 

English

Numeric

English

 

Numeric

 

 

 

 

Code

 

 

Code

 

 

 

ComADR

1001

1 to 99

 

 

 

COMMUNICATIONS STATION ADDRESS—This

 

 

 

 

 

 

 

is a number that is assigned to a controller that is

 

 

 

 

 

 

 

to be used with the communications option. This

 

 

 

 

 

 

 

number will be its address. This parameter is also

 

 

 

 

 

 

 

used for the IR communications link.

 

 

 

 

 

 

 

 

COMSTA

1002

 

 

 

 

 

COMMUNICATIONS SELECTION

 

 

DIS

0

 

 

DISABLE—Disables the communications option

 

 

MODB

1

 

 

MODBUS—Enable Modbus RTU communications

 

 

ETHR

2

 

 

ETHERNET—Enable Ethernet Communications

 

 

 

 

 

 

 

IRENAB

1003

DIS

0

 

 

INFRARED COMMUNICATIONS – Enables/

 

 

ENAB

1

 

 

Disables the IR Port.

 

 

 

 

 

 

 

 

BAUD

1004

 

 

 

 

 

BAUD RATE is the transmission speed in bits per

 

 

 

 

 

 

 

second. This value is used for both RS-485 and IR

 

 

 

 

 

 

 

Communications, but for IR Communications,

 

 

 

 

 

 

 

values below 19200 baud are interpreted as being

 

 

 

 

 

 

 

19200 baud.

 

 

4800

 

0

 

 

4800 BAUD

 

 

9600

 

 

 

 

 

 

1

 

 

9600 BAUD

 

 

19200

 

 

 

 

 

 

2

 

 

19200 BAUD

 

 

38400

 

 

 

 

 

 

3

 

 

38400 BAUD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

73