Configuration

Function Prompt

Selection or Range of Setting

Parameter

Lower Display

Upper Display

Definition

English

Numeric

English

Numeric

 

 

Code

 

Code

 

 

 

DEV

4

DEVIATION (PROCESS VARIABLE

 

 

 

 

MINUS SETPOINT)—Represents –100 %

 

 

 

 

to +100 % of the selected PV span in

 

 

 

 

engineering units.

 

 

 

 

Zero deviation will produce a center scale

 

 

 

 

(12 mA or 50 %) output. A negative deviation

 

 

 

 

equal in magnitude to the Auxiliary Output

 

 

 

 

High Scaling Factor will produce a low end

 

 

 

 

output (4 mA or 0 %) output. A positive

 

 

 

 

deviation equal in magnitude to the Auxiliary

 

 

 

 

Output Low Scaling Factor will produce a

 

 

 

 

high end output (20 mA or 100 %).

 

 

 

 

FOR EXAMPLE:

 

 

 

 

Input 1 = Type T High Thermocouple

 

 

 

 

PV range = –300 °F to +700 °F

 

 

 

 

PV span = 1000 °F

 

 

 

 

Deviation Range = –1000 °F to +1000 °F

 

 

 

 

Auxiliary Output Low Scale Value = 0.0

 

 

 

 

Auxiliary Output High Scale Value = 1000

 

 

 

 

If PV = 500 °F and SP = 650 °F

 

 

 

 

then Deviation Display = –150 °F, which

 

 

 

 

is

 

 

 

 

–7.5% of the Deviation Range, so

 

 

 

 

Auxiliary Output = 50% – 7.5% = 42.5%

 

 

OUT

5

OUTPUT—Represents the displayed

 

 

 

 

controller output in percent (%). Cannot be

 

 

 

 

used with

 

 

 

 

Three Position Step Control.

 

 

SP

6

SETPOINT—Represents the value of the

 

 

 

 

setpoint currently in use and is shown in the

 

 

 

 

same units as those used by the PV.

 

 

LSP 1

7

LOCAL SETPOINT ONE—Auxiliary output

 

 

 

 

represents Local Setpoint 1 regardless of

 

 

 

 

active setpoint.

 

 

LSP 2

8

LOCAL SETPOINT TWO—Auxiliary output

 

 

 

 

represents Local Setpoint 2 regardless of

 

 

 

 

active setpoint.

0PCT

902

Value in

 

AUXILIARY OUTPUT LOW SCALING

 

 

Engineering Units

 

FACTOR— This is a value in engineering

 

 

 

 

units used to represent all AUX OUT

 

 

 

 

parameters except Output.

 

 

 

 

For Output, this is a value in percent and can

 

 

 

 

be any value between –5 % and +105 %.

 

 

 

 

However, keep in mind that relay output

 

 

 

 

types can only be scaled 0 % to 100 %.

68

UDC2500 Universal Digital Controller Product Manual

4/07

Page 82
Image 82