| Configuration |
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Function Prompt |
| Selection or Range of Setting |
|
| Parameter | ||||
|
| Lower Display |
| Upper Display |
|
| Definition | ||||
|
| English | Numeri |
| English | Numeric |
|
|
|
|
|
|
|
| c Code |
|
| Code |
|
|
|
|
|
|
| EUHRDN | 206 |
| 0 to 9999 in |
|
|
| RATE | ||
|
|
|
|
| Engineering units |
|
|
| making a setpoint change, this is the rate at | ||
|
|
|
|
| per hour |
|
|
| which the controller will change from the | ||
|
|
|
|
|
|
|
|
| original setpoint down to the new one. The | ||
|
|
|
|
|
|
|
|
| ramping (current) setpoint can be viewed as | ||
|
|
|
|
|
|
|
|
| SPn in the lower display. | ||
|
|
|
|
|
|
|
|
| Entering a 0 will imply an immediate change | ||
|
|
|
|
|
|
|
|
| in Setpoint (i.e., no rate applies). | ||
|
|
|
|
|
|
|
|
|
| ||
|
| SPPROG | 207 |
| DIS | 0 |
|
| SETPOINT RAMP/SOAK PROGRAM— | ||
|
| (optional |
|
| ENAB | 1 |
|
| Available only with controllers that contain | ||
|
| feature) |
|
|
|
|
|
| this option. | ||
|
| SP Ramp |
|
|
|
|
|
| SP RAMP must be disabled. | ||
|
| must be |
|
|
|
|
|
| |||
|
| disabled for |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||||
|
| SP Program |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| Detailed information for the | ||
|
| prompts to |
|
|
|
|
|
| ATTENTION | ||
|
| appear. If |
|
|
|
|
|
| prompts for SP Programming may be found | ||
|
| SP Rate is |
|
|
|
|
|
| in Section 4.21 – Setpoint Programming. The | ||
|
| enabled, it |
|
|
|
|
|
| listing below is only for reference purposes. | ||
|
| does not |
|
|
|
|
|
|
|
|
|
|
| operate |
|
|
|
|
|
|
|
|
|
|
| while an SP |
|
|
|
|
|
|
|
|
|
|
| Program is |
|
|
|
|
|
|
|
|
|
|
| running. |
|
|
|
|
|
|
|
|
|
|
| STRSEG | 208 |
| 1 to 11 |
|
| Start Segment Number | |||
|
| ENDSEG | 209 |
| 2 to 12 (always end in |
|
|
| End Segment Number | ||
|
|
|
|
| a soak segment) | 2 |
|
|
|
|
|
|
|
|
|
| SOK 2 |
|
|
|
|
| |
|
|
|
|
| 4 |
|
|
|
|
| |
|
|
|
|
| SOK 4 |
|
|
|
|
| |
|
|
|
|
| 6 |
|
|
|
|
| |
|
|
|
|
| SOK 6 |
|
|
|
|
| |
|
|
|
|
| 8 |
|
|
|
|
| |
|
|
|
|
| SOK 8 |
|
|
|
|
| |
|
|
|
|
| 10 |
|
|
|
|
| |
|
|
|
|
| SOK 10 |
|
|
|
|
| |
|
|
|
|
| 12 |
|
|
|
|
| |
|
|
|
|
| SOK 12 |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
|
| RPUNIT | 210 |
|
|
|
|
| Engineering Units for Ramp Segments | ||
|
|
|
|
| TIME | 0 |
|
| TIME in hours:minutes | ||
|
|
|
|
| 1 |
|
| RATE in Enineering units per minute | |||
|
|
|
|
| 2 |
|
| RATE in Enineering units per hour | |||
|
|
|
|
|
|
|
|
|
| ||
|
| RECYCL | 211 |
| 0 to 100 recycles |
|
|
| Number of Program Recycles | ||
|
|
|
|
|
|
|
|
|
| ||
|
| SOKDEV | 212 |
| 0 to 100 |
|
|
| Guaranteed Soak Deviation Value | ||
|
|
|
|
|
|
|
|
| |||
|
| PG END | 213 | LAST (Hold at last | 0 |
|
| Program Termination State | |||
|
|
|
|
| SP) FSAF (Manual | 1 |
|
|
|
|
|
|
|
|
|
| mode/failsafe) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 41 |