Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function Prompt

 

Selection or Range of Setting

 

 

Parameter

 

 

Lower Display

 

Upper Display

 

 

Definition

 

 

English

Numeri

 

English

Numeric

 

 

 

 

 

 

 

 

c Code

 

 

Code

 

 

 

 

 

 

 

EUHRDN

206

 

0 to 9999 in

 

 

 

RATE DOWN—Rate down value. When

 

 

 

 

 

Engineering units

 

 

 

making a setpoint change, this is the rate at

 

 

 

 

 

per hour

 

 

 

which the controller will change from the

 

 

 

 

 

 

 

 

 

original setpoint down to the new one. The

 

 

 

 

 

 

 

 

 

ramping (current) setpoint can be viewed as

 

 

 

 

 

 

 

 

 

SPn in the lower display.

 

 

 

 

 

 

 

 

 

Entering a 0 will imply an immediate change

 

 

 

 

 

 

 

 

 

in Setpoint (i.e., no rate applies).

 

 

 

 

 

 

 

 

 

 

 

 

SPPROG

207

 

DIS

0

 

 

SETPOINT RAMP/SOAK PROGRAM

 

 

(optional

 

 

ENAB

1

 

 

Available only with controllers that contain

 

 

feature)

 

 

 

 

 

 

this option.

 

 

SP Ramp

 

 

 

 

 

 

SP RAMP must be disabled.

 

 

must be

 

 

 

 

 

 

DISABLE—Disables setpoint programming.

 

 

disabled for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENABLE—Enables setpoint programming.

 

 

SP Program

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detailed information for the

 

 

prompts to

 

 

 

 

 

 

ATTENTION

 

 

appear. If

 

 

 

 

 

 

prompts for SP Programming may be found

 

 

SP Rate is

 

 

 

 

 

 

in Section 4.21 – Setpoint Programming. The

 

 

enabled, it

 

 

 

 

 

 

listing below is only for reference purposes.

 

 

does not

 

 

 

 

 

 

 

 

 

 

 

operate

 

 

 

 

 

 

 

 

 

 

 

while an SP

 

 

 

 

 

 

 

 

 

 

 

Program is

 

 

 

 

 

 

 

 

 

 

 

running.

 

 

 

 

 

 

 

 

 

 

 

STRSEG

208

 

1 to 11

 

 

Start Segment Number

 

 

ENDSEG

209

 

2 to 12 (always end in

 

 

 

End Segment Number

 

 

 

 

 

a soak segment)

2

 

 

 

 

 

 

 

 

 

 

SOK 2

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

SOK 4

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

SOK 6

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

SOK 8

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

SOK 10

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

SOK 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPUNIT

210

 

 

 

 

 

Engineering Units for Ramp Segments

 

 

 

 

 

TIME

0

 

 

TIME in hours:minutes

 

 

 

 

 

EU-M

1

 

 

RATE in Enineering units per minute

 

 

 

 

 

EU-H

2

 

 

RATE in Enineering units per hour

 

 

 

 

 

 

 

 

 

 

 

 

RECYCL

211

 

0 to 100 recycles

 

 

 

Number of Program Recycles

 

 

 

 

 

 

 

 

 

 

 

 

SOKDEV

212

 

0 to 100

 

 

 

Guaranteed Soak Deviation Value

 

 

 

 

 

 

 

 

 

 

 

PG END

213

LAST (Hold at last

0

 

 

Program Termination State

 

 

 

 

 

SP) FSAF (Manual

1

 

 

 

 

 

 

 

 

 

 

mode/failsafe)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

41

Page 55
Image 55