Modbus Read, Write and Override Parameters plus Exception Codes
Parameter | Register | Data | Access |
|
|
| Data Range or | |
Description | Address | Type |
|
|
|
| Enumerated Selection | |
|
|
|
|
|
|
|
|
|
| Hex | Decimal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Digital Input | 00BA | 186 | INT | R/W |
| 0 = None | ||
#1 |
|
|
|
|
| 1 = To Manual | ||
|
|
|
|
| 2 | = To Local Setpoint #1 | ||
|
|
|
|
| 3 | = To Local Setpoint #2 | ||
|
|
|
|
| 4 | = To Direct Action | ||
|
|
|
|
| 5 | = To Hold Ramp | ||
|
|
|
|
| 6 | = To PID Set #2 | ||
|
|
|
|
| 7 | = To Run Ramp | ||
|
|
|
|
| 8 | = To Begin | ||
|
|
|
|
| 9 | = No I (Reset) | ||
|
|
|
|
| 10 | = To Manual Failsafe | ||
|
|
|
|
|
|
|
| Output |
|
|
|
|
| 11 | = Disable Keyboard | ||
|
|
|
|
| 12 | = To Timer | ||
|
|
|
|
| 13 | = Initiate Limit Cycle | ||
|
|
|
|
|
|
|
| Tuning |
|
|
|
|
| 14 | = Setpoint Initialization | ||
|
|
|
|
|
|
|
| (SP=PV) |
|
|
|
|
| 15 | = To RSP | ||
|
|
|
|
| 16 | = Manual Latching | ||
|
|
|
|
| 17 | = Output 1 tracks Input 2 | ||
|
|
|
|
| 18 | = Start/Restart SP Ramp or | ||
|
|
|
|
|
|
|
| SP Program |
Digital Input | 00BC | 188 | INT | R/W |
| 0 = Disable | ||
#1 |
|
|
|
|
| 1 = +PID2 | ||
Combinations |
|
|
|
|
| 2 = +Direct | ||
|
|
|
|
| 3 | = +LSP2 | ||
|
|
|
|
| 4 | = +LSP1 | ||
|
|
|
|
| 5 | = +Run | ||
Digital Input | 00BB | 187 | INT | R/W |
| Same as Digital Input #1 | ||
#2 * |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Digital Input | 00BD | 189 | INT | R/W |
| Same as Digital Input #1 | ||
#2 |
|
|
|
|
|
| Combinations | |
Combinations |
|
|
|
|
|
|
|
|
* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
* Auxiliary Output and Digital Input #2 are mutually exclusive.
212 | UDC2500 Universal Digital Controller Product Manual | 4/07 |