Configuration

3.8 Output Set Up Group

Introduction

This group deals with various output types in the controller, the Digital Output Status and the Current Output operation.

ATTENTION The Tuning Group is automatically configured to have two PID sets when a Duplex Control Algorithm is selected.

Function Prompts

Table 3-8 OUTPUT Group (Numeric Code 500) Function Prompts

 

Function Prompt

Selection or Range of Setting

 

 

Parameter

 

Lower Display

Upper Display

 

 

Definition

 

English

Numeric

 

English

Numeric

 

 

 

 

 

 

Code

 

 

Code

 

 

 

 

 

OUTALG

501

 

 

 

 

 

The OUTPUT ALGORITHM lets you select

 

 

 

 

 

 

the type of output you want. Not applicable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with Control algorithm prompt TPSC

 

 

 

 

 

 

 

 

(Three Position Step Control).

 

 

 

 

 

 

 

 

Selections are hardware dependent. For

 

 

 

 

 

 

 

 

example, if the controller does not have a

 

 

 

 

 

 

 

 

current output, then none of the prompts for

 

 

 

 

 

 

 

 

Output Algorithms that need a current output

 

 

 

 

 

 

 

 

will appear. Likewise, if the controller does

 

 

 

 

 

 

 

 

not have a relay output, then none of the

 

 

 

 

 

 

 

 

prompts that need a relay output will appear.

 

 

 

 

 

 

 

 

 

For all Duplex Output forms,

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

PID heat parameters apply for controller

 

 

 

 

 

 

 

 

output greater than 50 %; PID cool

 

 

 

 

 

 

 

 

parameters apply for controller output less

 

 

 

 

 

 

 

 

than 50 %.

 

 

 

 

RLY

0

 

 

TIME SIMPLEX—This output algorithm uses

 

 

 

 

 

 

 

Digital Output 1 for Time Proportional

 

 

 

 

 

 

 

 

Control. The output is updated per the Loop

 

 

 

 

 

 

 

 

sampling rate selection. Time Proportional

 

 

 

 

 

 

 

 

Output has a resolution of 4.44 msec. Cycle

 

 

 

 

 

 

 

 

Time is adjustable from 1 to 120 seconds.

 

 

 

 

RLY2

1

 

 

TIME SIMPLEX—This output algorithm uses

 

 

 

 

 

 

 

Digital Output 2 for Time Proportional

 

 

 

 

 

 

 

 

Control. The output is updated per the Loop

 

 

 

 

 

 

 

 

sampling rate selection. Time Proportional

 

 

 

 

 

 

 

 

Output has a resolution of 4.44 msec. Cycle

 

 

 

 

 

 

 

 

Time is adjustable from 1 to 120 seconds.

 

 

 

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

51