Troubleshooting/Service

Procedure #6

Table 7-10explains how to troubleshoot Alarm Relay Output failure.

Table 7-10 Troubleshooting Alarm Relay Output Failure

Step

What to do

How to do it

1

Check the alarm configuration

Reconfigure if necessary.

 

data. If it is correct, check the

Refer to Section 3 - Configuration for

 

field wiring.

details.

2Check that the applicable alarm relay actuates properly depending on what you have set at prompt AxSxTYPE.

If it does, check the field wiring.

3Check the contacts.

4Change the relay and/or the current output board.

5Change MCU board.

If the alarm type is set for PV, place the controller in manual mode. Vary the input to raise and lower the PV around the setpoint. Listen for a click from the relay as the PV moves in either direction and note that the proper ALM1 or ALM2 is lit.

EXAMPLE: If the alarm is set for MAN, put the controller into manual mode. The alarm light is ON. Put the controller into automatic mode and the alarm light is OFF.

Make sure the NO or NC contact wiring is correct.

Refer to Section 2 - Installation for relay contact information.

Installation instructions supplied with the new relay or board.

Installation instructions supplied with the new board.