| Troubleshooting/Service |
|
|
|
|
|
|
| |
| Lower |
| Reason for Failure |
| How to Correct the Problem | |
| Display |
|
|
|
|
|
| IN2RNG |
| Input 2 out of range. The remote input |
| Same as IN1RNG above. | |
|
|
| is outside the range limits. |
|
|
|
|
|
|
|
|
| |
| IN2_FL |
| Two consecutive failures of input 2 |
| Same as IN1FL above. | |
|
|
| integration. i.e., cannot make analog |
|
|
|
|
|
| to digital conversion. |
|
|
|
| CNFERR |
| • PV low limit is > PV high limit |
| 1. Check the configuration for each item and | |
|
|
| • SP low limit is > SP high limit |
| reconfigure if necessary. | |
|
|
| • Output low limit > Output high limit |
|
|
|
|
|
|
|
|
| |
| PV LIM |
| PV out of range. |
| 1. Make sure the input signal is correct. | |
|
|
| PV = INP1 x RATIO1+ INP1 BIAS |
| 2. Make sure the Ratio and Bias settings are | |
|
|
|
|
| ||
|
|
|
|
| correct. | |
|
|
|
|
| 3. Recheck the calibration. Use Bias of 0.0 | |
|
|
|
|
|
| |
| RV LIM |
| The result of the formula shown below |
| 1. Make sure the input signal is correct. | |
|
|
| is beyond the range of the remote |
| 2. Make sure the Ratio2 and Bias2 settings are | |
|
|
| variable. |
| ||
|
|
|
| correct. | ||
|
|
| RV = INP2 X RATIO + BIAS |
| ||
|
|
|
| 3. Recheck the calibration. Use a Ratio2 of 1.0 | ||
|
|
|
|
| ||
|
|
|
|
| and a Bias2 of 0.0. | |
|
|
|
|
|
| |
| SEGERR |
| Setpoint Program start segment |
| Check SP Program configuration, subsection 3.5 | |
|
|
| number is less than ending segment |
| Set up Group SPPROG function prompts | |
|
|
| number. |
| “STRSEG” and “ENDSEG”. | |
|
|
|
|
|
| |
| TCWARN |
| The Thermocouple is starting to |
| This diagnostic message means that the | |
|
|
| burnout. |
| controller has detected that the thermocouple is | |
|
|
|
|
| starting to burnout. This error message may also | |
|
|
|
|
| be created if the resistance of the wires used to | |
|
|
|
|
| connect the thermocouple to the instrument is | |
|
|
|
|
| above 100 ohms. | |
|
|
|
|
|
| |
| TCFAIL |
| The Thermocouple is in imminent |
| This diagnostic message means that the | |
|
|
| danger of burning out. |
| controller has detected that the thermocouple | |
|
|
|
|
| will soon fail. User should consider replacing the | |
|
|
|
|
| thermocouple as soon as possible. This | |
|
|
|
|
| message will also be generated if the resistance | |
|
|
|
|
| of the wires used to connect the thermocouple to | |
|
|
|
|
| the instrument is above 180 ohms. | |
|
|
|
|
| ||
| OUT1FL |
| Current Output is less than 3.5 mA. | The current output is open circuit. Check the | ||
|
|
|
|
| field wiring. See Procedure #2. | |
|
|
|
|
| ||
| OUT2FL |
| Auxiliary Output is less than 3.5 mA. | The auxiliary output is open circuit. Check the | ||
|
|
|
|
| field wiring. See Procedure #10. | |
|
|
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 163 |