Input Calibration

Sensor Type

PV Input Range

 

Range Values

 

°F

 

°C

0 %

100 %

S

0 to 3100

 

–18 to1704

 

–0.092 mV

17.998 mV

 

 

 

 

 

 

 

T

-300 to 700

 

–184 to 371

 

–5.341 mV

19.097 mV

 

 

 

 

 

 

 

T (low)

-200 to 500

 

–129 to 260

 

–4.149 mV

12.574 mV

 

 

 

 

 

 

 

W5W26

0 to 4200

 

–18 to 2315

 

–0.234 mV

37.075 mV

 

 

 

 

 

 

 

W5W26 (low)

0 to 2240

 

–18 to 1227

 

–0.234 mV

22.283 mV

 

 

 

 

 

 

 

RP20-RP40

32 to 3216

 

0 to1880

 

0.000 mV

4.933 mV

 

 

 

 

 

 

 

Thermocouple

–50 to 150

 

–46 to 66

 

–1.54 mV

4.62 mV

Differential *

 

 

 

 

 

 

Honeywell

 

 

 

 

 

 

Radiamatic

 

 

 

 

 

 

Type RH

0 to 3400

 

–18 to 1871

 

0.00 mV

57.12 mV

Type RI **

0 to 3400

 

–18 to 1871

 

0.00 mV

60.08 mV

RTD

 

 

 

 

 

 

Alpha = 0.00385 per

 

 

 

 

 

 

IEC-60751 (1995)

 

 

 

 

 

 

100 ohms

–300 to 1200

 

–184 to649

 

25.202 ohms

329.289 ohms

100 ohms (low)

–300 to 300

 

–184 to149

 

25.202 ohms

156.910 ohms

200 ohms

–300 to 1200

 

–184 to649

 

50.404 ohms

658.578 ohms

500 ohms

–300 to 1200

 

–184 to649

 

126.012 ohms

1646.445 ohms

Linear

 

 

 

 

 

 

Milliamps

4 to 20 mA

 

4.00 mA

20.00 mA

 

0 to 20 mA

 

0.00 mA

20.00 mA

Millivolts

0 to

10 mV

 

0.00 mV

10.00 mV

 

0 to

50 mV

 

0.00 mV

50.00 mV

 

0 to 100 mV

 

0.00 mV

100.00 mV

Volts

1 to

5 Volts

 

1.00 Volts

5.00 Volts

 

0 to

5 Volts

 

0.00 Volts

5.00 Volts

 

0 to 10 Volts

 

0.00 Volts

10.00 Volts

 

 

 

 

 

 

 

*The Factory Calibrated millivolt values for the Thermocouple Differential Input are for a pair of J thermocouples at an ambient temperature mean of 450°F / 232°C. Other thermocouple types and ambient temperature means may be accomplished via Field Calibration of the input, with the range value limits being –4 mV to +16 mV for the zero and span values.

**The range values for Radiamatic Type RI are customer configurable within the limits shown.

138

UDC2500 Universal Digital Controller Product Manual

4/07

Page 152
Image 152
Honeywell UDC2500 Sensor Type PV Input Range Range Values 100 %, W5W26 low, RP20-RP40, Honeywell Radiamatic Type RH