Output Calibration
Procedure
The procedure for calibrating the Current Output is listed in Table
Table 6-2 Current Output Calibration Procedure
(Numeric Code 30000)
Step
Operation
Press
Result
1 | Enter Calibration | Setup | Upper Display = CAL ( - - - - ) |
| Mode |
| Lower Display = CURENT (30000) |
until you see
2 | Calibrate 0 % | Function |
|
|
or
You will see:
Upper Display = A Value
Lower Display = ZROVAL (30001)
Until the desired 0 % output is read on the milliammeter, use the values shown below depending on the action of your controller. Normally, this will be the setting that produces 4 mA.
3 | Calibrate 100 % | Function |
|
|
or
This stores the 0 % value and you will see:
Upper Display = A Value
Lower Display = SPNVAL (30002)
Until the desired 100 % output is read on the milliammeter, use the values shown below depending on the action of your controller. Normally, this will be the setting that produces 20 mA.
4Exit the Calibration Mode
Function
Lower
Display
The controller stores the span value.
To exit the calibration mode.