Monitoring and Operating the Controller

Function

 

Press

Result

Viewing the present

 

 

 

Upper Display = PV value

 

Lower

 

ramp or soak

 

Display

 

Lower Display = XXHH.MM

segment number

 

 

 

Time remaining in the SEGMENT in hours and

until you see

and time

 

 

 

 

minutes. XX = The current number, 1 to 12.

Viewing the number

 

 

 

Upper Display = PV value

 

Lower

 

of cycles left in the

 

 

Lower Display = REC_XX

 

Display

 

program

 

 

 

Number of cycles remaining in the setpoint

until you see

 

 

program. X = 0 to 99

 

 

 

 

End Program

 

 

 

When the final segment is completed, the

 

 

 

 

RUN” in the upper display either changes to

 

 

 

 

HOLD” (if configured for HOLD state), or

 

 

 

 

disappears (if configured for disable of setpoint

 

 

 

 

programming).

 

 

 

 

The controller either operates at the last

 

 

 

 

setpoint in the program or goes into manual

 

 

 

 

mode/failsafe output.

Disable Program

 

 

 

See Section 3 – Configuration Group

 

 

 

 

“SPPROG” for details.

 

 

 

 

 

Power outage

ATTENTION If power is lost during a program, upon power-up the controller will be in hold and the setpoint value will be the setpoint value prior to the beginning of the setpoint program. The program is placed in hold at the beginning. The mode will be as configured under “PWR UP” in the “CONTROL” group.

Digital input (remote switch) operation

Program can be placed in RUN or HOLD state through a remote dry contact connected to optional digital input terminals, as follows:

RUN—contact closure places Program in RUN state, OR HOLD—contact closure places Program in HOLD state

Opening the contact will cause the Controller to revert to its original state.