Installation
2.7 Wiring Diagrams
Identify Your Wiring Requirements
To determine the appropriate diagrams for wiring your controller, refer to the model number interpretation in this section. The model number of the controller is on the outside of the case.
Universal Output Functionality and Restrictions
Instruments with multiple outputs can be configured to perform a variety of output types and alarms. For example, an instrument with one current output and two relays can be configured to provide any one of the following:
1)Current Simplex with two alarm relays
2)Current Duplex 100% with two alarm relays
3)Time Simplex with one alarm relay
4)Time Duplex with no alarm relays
5)Three Position Step Control with no alarm relays
These selections may all be made via the keyboard and by wiring to the appropriate output terminals; there are no internal jumpers or switches to change. This flexibility allows a customer to stock a single instrument which is able to handle a variety of applications.
Table
Output 1 is HEAT and Output 2 is COOL.
In Table
Output 1 is OPEN and Output 2 is CLOSE.
In Table