| Configuration |
|
|
|
|
|
|
|
|
|
|
| |
| Function Prompt |
| Selection or Range of Setting |
|
| Parameter | ||||
| Lower Display |
| Upper Display |
|
| Definition | ||||
| English | Numeric |
| English | Numeric |
|
|
|
|
|
|
| Code |
|
| Code |
|
|
|
|
|
|
|
|
| TWO | 1 |
|
| TWO LOCAL | ||
|
|
|
|
|
|
|
| lets you switch between two local setpoints | ||
|
|
|
|
|
|
|
| using the SETPOINT SELECT key. | ||
|
|
|
|
|
|
|
|
|
| |
| RSPSRC | 804 |
|
|
|
|
| REMOTE SETPOINT SOURCE— This | ||
|
|
|
|
|
|
|
| selection lets you switch between the local | ||
|
|
|
|
|
|
|
| and remote setpoints using the | ||
|
|
|
|
|
|
|
| SETPOINT SELECT key. | ||
|
|
|
| NONE | 0 |
|
| |||
|
|
|
|
|
| INPUT | ||||
|
|
|
| INP2 | 1 |
|
| |||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
| SP TRK | 805 |
|
|
|
|
| SETPOINT | ||
|
|
|
|
|
|
|
| can be configured to track either PV or RSP | ||
|
|
|
|
|
|
|
| as listed below. Not configurable when Auto | ||
|
|
|
|
|
|
|
| Bias is set. | ||
|
|
|
|
|
|
|
|
| For selections other than | |
|
|
|
|
|
|
|
| ATTENTION | ||
|
|
|
|
|
|
|
| NONE, LSP is | stored in nonvolatile memory | |
|
|
|
|
|
|
|
| only when there is a mode change; i.e., | ||
|
|
|
|
|
|
|
| when switching from RSP to LSP or from | ||
|
|
|
|
|
|
|
| Manual to Automatic. If power is lost, then | ||
|
|
|
|
|
|
|
| the current LSP value is also lost. | ||
|
|
|
| NONE | 0 |
|
| NO | ||
|
|
|
|
|
|
|
| not configured, the LSP will not be altered | ||
|
|
|
|
|
|
|
| when transfer from RSP to LSP is made. | ||
|
|
|
| PROC | 1 |
|
| PROCESS VARIABLE | ||
|
|
|
|
|
|
|
| tracks the PV when in manual. | ||
|
|
|
| RSP | 2 |
|
| |||
|
|
|
|
|
|
|
| when in automatic. When the controller | ||
|
|
|
|
|
|
|
| transfers out of remote setpoint, the last | ||
|
|
|
|
|
|
|
| value of the remote setpoint (RSP) is | ||
|
|
|
|
|
|
|
| inserted into the local setpoint. | ||
| PWR UP | 806 |
|
|
|
|
| POWER UP CONTROLLER MODE | ||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| mode and setpoint the controller will use | ||
|
|
|
|
|
|
|
| when the controller restarts after a power | ||
|
|
|
|
|
|
|
| loss. | ||
|
|
|
| MAN | 0 |
|
| MANUAL, | ||
|
|
|
|
|
|
|
| will use manual mode with the local setpoint | ||
|
|
|
|
|
|
|
| displayed. | ||
|
|
|
| ALSP | 1 |
|
| AUTOMATIC MODE, LAST | ||
|
|
|
|
|
|
|
| up, the controller will use automatic mode | ||
|
|
|
|
|
|
|
| with the last local setpoint used before power | ||
|
|
|
|
|
|
|
| down displayed. | ||
|
|
|
|
|
|
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 63 |