Troubleshooting/Service
Procedure #5
Table
Table
Output Failure
Step | What to do | How to do it |
1 | Make sure the controller is configured | Make Output Algorithm Set Up group function |
| for Time/Current or Current/Time | prompt OUT ALG = TCUR or CURT. |
| Proportional output. | Refer to Section 3 – Configuration. |
|
| |
2 | Check the field wiring. | Make sure the NO or NC contact wiring selection |
|
| is correct. |
|
| Refer to Section 2 - Installation for details. |
3 | Check the relay output. | Put the controller into Manual mode. Vary the |
|
| output above and below the present value. |
|
| Observe OUT1 indicator on the operator interface. |
|
| Listen for a click from the relay when the OUT1 |
|
| indicator changes state. |
4 | Check the Current Proportional | Put the controller into Manual mode and change |
| Output. | the output from 0 % to 100 % |
|
| milliammeter at the rear terminals to verify the |
|
| output. |
5 | Recalibrate the controller. | Refer to Section 6 - Output Calibration for details. |
6 | Change relay and/or Current Output | Installation instructions supplied with new board. |
| boards. |
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 169 |