Configuration
Function Prompt | Selection or Range of Setting |
|
| Parameter | |||
Lower Display |
| Upper Display |
|
| Definition | ||
English | Numeric | English | Numeric |
|
|
| |
| Code |
|
| Code |
|
|
|
|
| HOLD |
| 5 |
| TO | |
|
|
|
|
|
| Setpoint Program or Setpoint Ramp. When | |
|
|
|
|
|
| contact reopens, the controller starts from | |
|
|
|
|
|
| the Hold point of the Ramp/Program unless | |
|
|
|
|
|
| the Ramp/Program was not previously | |
|
|
|
|
|
| started via the RUN/HOLD key. | |
|
|
|
|
|
| This selection applies to either loop. | |
|
| PID2 |
| 6 |
| TO | |
|
|
|
|
| 2. |
| |
|
| RUN |
| 7 |
| ||
|
|
|
|
|
| Ramp or Program. Upper left character | |
|
|
|
|
|
| blinks “R”. Reopening the contact puts | |
|
|
|
|
|
| controller in HOLD mode. | |
|
|
|
|
|
| This selection applies to either loop. | |
|
| Begn |
| 8 |
| EXTERNAL SP PROGRAM RESET— | |
|
|
|
|
|
| Contact closure resets SP Program back to | |
|
|
|
|
|
| the beginning of the first segment in the | |
|
|
|
|
|
| program and places the program in the | |
|
|
|
|
|
| HOLD mode. Program cycle number is not | |
|
|
|
|
|
| affected. Reopening switch has no effect. | |
|
|
|
|
|
| This selection applies to either loop. | |
|
|
|
|
|
|
| Once the last segment of the |
|
|
|
|
|
| ATTENTION | |
|
|
|
|
|
| setpoint program has timed out, the | |
|
|
|
|
|
| controller enters the mode of action specified | |
|
|
|
|
|
| in the configuration data and the program | |
|
|
|
|
|
| cannot be reset to the beginning of the first | |
|
|
|
|
|
| segment by digital input closure. | |
|
| NO I |
| 9 |
| INHIBIT INTEGRAL | |
|
|
|
|
|
| closure disables PID Integral (Reset) action. | |
|
| MNFS |
| 10 |
| MANUAL FAILSAFE | |
|
|
|
|
|
| goes to Manual mode, output goes to the | |
|
|
|
|
|
| Failsafe value. | |
|
|
|
|
|
|
| This will cause a bump in the |
|
|
|
|
|
| ATTENTION | |
|
|
|
|
|
| output when | switching from Automatic to |
|
|
|
|
|
| Manual. The switch back from Manual to | |
|
|
|
|
|
| Automatic is bumpless. When the switch is | |
|
|
|
|
|
| closed, the output can be adjusted from the | |
|
|
|
|
|
| keyboard. | |
|
| LOCK |
| 11 |
| KEYBOARD | |
|
|
|
|
|
| disables all keys. Lower display shows | |
|
|
|
|
|
| LOCKED if a key is pressed. | |
|
|
|
|
|
|
|
|
70 | UDC2500 Universal Digital Controller Product Manual | 4/07 |