Configuration

Function Prompt

Selection or Range of Setting

 

 

Parameter

Lower Display

 

Upper Display

 

 

Definition

English

Numeric

English

Numeric

 

 

 

 

Code

 

 

Code

 

 

 

 

 

HOLD

 

5

 

TO HOLD—Contact closure suspends

 

 

 

 

 

 

Setpoint Program or Setpoint Ramp. When

 

 

 

 

 

 

contact reopens, the controller starts from

 

 

 

 

 

 

the Hold point of the Ramp/Program unless

 

 

 

 

 

 

the Ramp/Program was not previously

 

 

 

 

 

 

started via the RUN/HOLD key.

 

 

 

 

 

 

This selection applies to either loop.

 

 

PID2

 

6

 

TO PID2—Contact closure selects PID Set

 

 

 

 

 

2.

 

 

 

RUN

 

7

 

RUN—Contact closure starts a stopped SP

 

 

 

 

 

 

Ramp or Program. Upper left character

 

 

 

 

 

 

blinks “R”. Reopening the contact puts

 

 

 

 

 

 

controller in HOLD mode.

 

 

 

 

 

 

This selection applies to either loop.

 

 

Begn

 

8

 

EXTERNAL SP PROGRAM RESET

 

 

 

 

 

 

Contact closure resets SP Program back to

 

 

 

 

 

 

the beginning of the first segment in the

 

 

 

 

 

 

program and places the program in the

 

 

 

 

 

 

HOLD mode. Program cycle number is not

 

 

 

 

 

 

affected. Reopening switch has no effect.

 

 

 

 

 

 

This selection applies to either loop.

 

 

 

 

 

 

 

Once the last segment of the

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

setpoint program has timed out, the

 

 

 

 

 

 

controller enters the mode of action specified

 

 

 

 

 

 

in the configuration data and the program

 

 

 

 

 

 

cannot be reset to the beginning of the first

 

 

 

 

 

 

segment by digital input closure.

 

 

NO I

 

9

 

INHIBIT INTEGRAL (RESET)—Contact

 

 

 

 

 

 

closure disables PID Integral (Reset) action.

 

 

MNFS

 

10

 

MANUAL FAILSAFE OUTPUT—Controller

 

 

 

 

 

 

goes to Manual mode, output goes to the

 

 

 

 

 

 

Failsafe value.

 

 

 

 

 

 

 

This will cause a bump in the

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

output when

switching from Automatic to

 

 

 

 

 

 

Manual. The switch back from Manual to

 

 

 

 

 

 

Automatic is bumpless. When the switch is

 

 

 

 

 

 

closed, the output can be adjusted from the

 

 

 

 

 

 

keyboard.

 

 

LOCK

 

11

 

KEYBOARD LOCKOUT—Contact closure

 

 

 

 

 

 

disables all keys. Lower display shows

 

 

 

 

 

 

LOCKED if a key is pressed.

 

 

 

 

 

 

 

 

70

UDC2500 Universal Digital Controller Product Manual

4/07

Page 84
Image 84
Honeywell UDC2500 manual External SP Program Reset, Inhibit Integral RESET-Contact, Manual Failsafe OUTPUT-Controller