Honeywell UDC2500 manual Setting Failsafe Mode, Setpoint Rate/Ramp/Program Overview, PV Hot Start

Models: UDC2500

1 243
Download 243 pages 28.29 Kb
Page 129
Image 129

Monitoring and Operating the Controller

4.17 Setting Failsafe Mode

Introduction

You can set the Failsafe Mode to be Latching or Non-Latching.

Set Failsafe Mode

Table 4-23 Procedure for Setting a Failsafe Mode

Step

Operation

Press

Result

1Select Control Set-up Group

2Select Failsafe

Function Prompt

Setup

Function

Until you see:

Upper Display = SET

Lower Display = CONTRL

You will see: Upper Display =

LACH (Controller goes to manual and output goes to failsafe value)

NO L (Controller mode does not change and output goes to failsafe value)

Lower Display = FSMODE

3

Select a value

or

To select a failsafe mode in the upper display.

4

Return to Normal

 

At power up, the output will go to the value set.

Lower

 

Display

Display

 

 

 

 

 

4.18 Setpoint Rate/Ramp/Program Overview

Introduction

The Setpoint Ramp configuration group lets you enable and configure any of the following:

SPRATE – a specific rate of change for any local setpoint change. (Subsection 4.20)

SPRAMP – a single setpoint ramp that occurs between the current local setpoint and a final local setpoint over a time interval of 1 to 255 minutes. (Subsection 4.19)

SPPROG – a ramp/soak profile in a 12-segment program. (Subsection 4.21)

This section explains the operation of each selection and configuration reference where necessary.

PV Hot Start

This is a standard feature. At power-up, the setpoint is set to the current PV value and the Rate or Ramp or Program then starts from this value.

4/07

UDC2500 Universal Digital Controller Product Manual

115

Page 129
Image 129
Honeywell UDC2500 manual Setting Failsafe Mode, Setpoint Rate/Ramp/Program Overview, PV Hot Start, Lower Display = Fsmode