Modbus Read, Write and Override Parameters plus Exception Codes

10.7.8Control

Table 10-16lists all the register addresses and ranges or selections for the function prompts in Set-up Group Control.

 

 

Table 10-16 Set-up Group – Control

 

Parameter

Register

Data

Access

 

Data Range or

Description

Address

Type

 

 

Enumerated Selection

 

Hex

Decimal

 

 

 

 

 

Tuning

00AC

172

INT

R/W

0 = One set only

Parameter

 

 

 

 

1

= 2 sets keyboard selected

Selection

 

 

 

 

2

= 2 sets with PV automatic

 

 

 

 

 

 

switchover

 

 

 

 

 

 

3

= 2 sets with setpoint (SP)

 

 

 

 

 

 

automatic switchover

Automatic

0038

056

FP

R/W

Within the PV Range in

Switchover

 

 

 

 

engineering units

Value (used with

 

 

 

 

 

 

 

172 selection 2

 

 

 

 

 

 

 

or 3)

 

 

 

 

 

 

 

Local Setpoint

00AD

173

INT

R/W

0 = One Local Setpoint

Source (Number

 

 

 

 

1

= Two Local Setpoints

of LSPs)

 

 

 

 

 

 

 

Power Up Mode

0082

130

INT

R/W

 

Control

Setpoint

Recall

 

 

 

 

 

Mode

Mode

 

 

 

 

 

0

= MAN

LSP

 

 

 

 

 

1

= AUTO

LSP

 

 

 

 

 

2

= AUTO

Last RSP

 

 

 

 

 

3

= LAST

Last SP

 

 

 

 

 

4

= LAST

Last Local SP

RSP Source

0083

131

INT

R/W

0 = None

 

 

 

 

 

 

1

= Input 2

 

Setpoint

008A

138

INT

R/W

0 = None

 

Tracking

 

 

 

 

1

= LSP = PV (when in

 

 

 

 

 

Manual)

 

 

 

 

 

 

2

= LSP = RSP (when

 

 

 

 

 

switched)

 

Control Setpoint

0007

007

FP

R/W

0 to 100% of PV

High Limit

 

 

 

 

(engineering units)

Control Setpoint

0008

008

FP

R/W

0 to 100% of PV

Low Limit

 

 

 

 

(engineering units)

Control Output

0087

135

INT

R/W

0 = Direct

 

Direction

 

 

 

 

1

= Reverse

 

4/07

UDC2500 Universal Digital Controller Product Manual

209

Page 223
Image 223
Honeywell UDC2500 manual Set-up Group Control