Configuration

Function Prompt

Selection or Range of

 

Parameter

 

Lower Display

Setting

 

Definition

 

 

 

Upper Display

 

 

 

 

English

Numeric

English

Numeric

 

 

 

 

 

Code

 

Code

 

 

 

 

TX_DLY

1005

1 to 500

 

TX DELAY—Configurable response-delay timer

 

 

milliseconds

 

allows you to force the UDC to delay its response

 

 

 

 

for a time period of from 1 to 500 milliseconds

 

 

 

 

compatible with the host system

 

 

 

 

 

hardware/software. This parameter is also used for

 

 

 

 

the IR communications link.

 

 

 

 

 

 

 

WS_FLT

1006

 

 

Defines word/byte order of floating point data for

 

 

 

 

communications. Byte values:

 

 

 

 

 

 

0

1

2

3

 

 

 

 

seeeeeee emmmmmmm mmmmmmmm mmmmmmmm

 

 

 

 

Where:

 

 

 

 

 

 

 

s = sign, e = exponent, m = mantissa bit

 

 

 

FP B

0

0

1

2

3

 

 

FPBB

1

1

0

3

2

 

 

FP L

2

3

2

1

0

 

 

FPLB

3

2

3

0

1

 

 

 

 

 

 

SDENAB

1007

DIS

0

SHED ENABLE—Disables/enables shed

 

 

 

ENAB

1

functionaliy.

 

 

 

 

 

 

 

 

SHDTIM

1008

0 to 255

 

SHED TIME—The number that represents how

 

 

Sample

 

many sample periods there will be before the

 

 

Periods

 

controller sheds from communications. Each

 

 

 

 

period equals 1/3 seconds; 0 equals No shed.

 

 

 

 

Note: If ComSTA is set to MODBUS and if

 

 

 

 

 

SHEDENAB is set to DISABL, Shed Time will not

 

 

 

 

be configurable.

 

 

 

 

 

 

 

SDMODE

1009

 

 

SHED CONTROLLER MODE AND OUTPUT

 

 

 

 

LEVEL—Determines the mode of local control you

 

 

 

 

want when the controller is shed from the

 

 

 

 

 

communications link.

 

 

 

 

LAST

0

LAST—SAME MODE AND OUTPUT—The

 

 

 

 

 

controller will return to the same mode (manual or

 

 

 

 

automatic) at the same output level that it had

 

 

 

 

before shed.

 

 

 

 

 

MAN

1

TO MAN—MANUAL MODE, SAME OUTPUT—

 

 

 

 

The controller will return to manual mode at the

 

 

 

 

same output level that it had before shed.

 

 

 

FSAFE

2

FSAFE—MANUAL MODE, FAILSAFE OUTPUT—

 

 

 

 

The controller will return to manual mode at the

 

 

 

 

output value selected at Control prompt FAILSAFE.

 

 

 

 

 

 

 

 

74

UDC2500 Universal Digital Controller Product Manual

4/07

Page 88