3.5 SP Ramp Set Up Group

Introduction

Set Point Ramp, Set Point Programs and Set Point Rates can be configured in this group.

A single Setpoint Ramp [SP RAMP] can be configured to occur between the current local setpoint and a final local setpoint over a time interval of from 1 to 255 minutes.

A Set Point Rate [SPRATE] lets you configure a specific rate of change for any local setpoint change.

A single Set Point Program [SP PROG] with up to 12 segments can be configured.

For more information on Set Point Rate, Ramp and Programming, see Sections 4.18 through 4.21.

You can start and stop the ramp/program using the RUN/HOLD key.

PV Hot Start is a configurable feature and means that, at initialization, the setpoint is set to the current PV value and the Ramp or Rate or Program then starts from this value.

Function Prompts

Table 3-5 SPRAMP Group (Numeric Code 200) Function Prompts

 

Function Prompt

Selection or Range of Setting

 

Parameter

 

Lower Display

Upper Display

 

Definition

 

English

Numeri

English

Numeric

 

 

 

 

c Code

 

Code

 

 

 

SP RAMP

201

DIS

0

 

SINGLE SETPOINT RAMP—Make a

 

SP Program

 

ENAB

1

 

selection to enable or disable the setpoint

 

 

 

 

 

ramp function. Make sure you configure a

 

must be

 

 

 

 

 

 

 

 

 

ramp time and a final setpoint value.

 

disabled for

 

 

 

 

 

 

 

 

 

 

 

SP Ramp

 

 

 

 

SP Programming must be disabled.

 

prompts to

 

 

 

 

DISABLE SETPOINT RAMP—Disables the

 

appear

 

 

 

 

 

 

 

 

 

 

setpoint ramp option.

 

 

 

 

 

 

ENABLE SETPOINT RAMP—Allows the

 

 

 

 

 

 

single setpoint ramp prompts to be shown.

 

 

 

 

 

 

 

 

TI MIN

202

0 to 255 minutes

 

 

SETPOINT RAMP TIME—Enter the number

 

 

 

 

 

 

of minutes desired to reach the final setpoint.

 

 

 

 

 

 

A ramp time of “0” implies an immediate

 

 

 

 

 

 

change of setpoint.

 

 

 

 

 

 

 