Installation

Pre-installation Information

If the controller has not been removed from its shipping carton, inspect the carton for damage then remove the controller.

Inspect the unit for any obvious shipping damage and report any damage due to transit to the carrier.

Make sure a bag containing mounting hardware is included in the carton with the controller.

Check that the model number shown on the inside of the case agrees with what you have ordered.

2.2Condensed Specifications

Honeywell recommends that you review and adhere to the operating limits listed in Table 2-1when you install your controller.

Table 2-1 Condensed Specifications

Specifications

Analog Inputs

Accuracy:

 

± 0.25% of full scale typical (± 1 digit for display)

 

Can be field calibrated to ± 0.05% of full scale typical

 

16-bit resolution typical

 

Sampling Rate: Both inputs are sampled six times per second

 

Temperature Stability: ± 0.01% of Full Scale span / ˚C change—typical

 

Input Impedance:

 

4-20 Milliampere Input: 250 ohms

 

0-10 Volt Input: 200K ohms

 

All Others: 10 megohms

 

Maximum Lead Wire Resistance:

 

Thermocouples: 50 ohms/leg

 

100 ohm, 200 ohm and 500 ohm RTD: 100 ohms/leg

 

100 ohm Low RTD: 10 ohms/leg

 

 

Analog Input Signal

Burnout Selections: Upscale, Downscale, Failsafe or None

Failure Operation

Thermocouple Health: Good, Failing, Failure Imminent or Failed

 

Failsafe Output Level: Configurable 0-100% of Output range

Stray Rejection

Common Mode

 

AC (50 or 60 Hz): 120 dB (with maximum source impedance of 100 ohms) or ± 1 LSB (least

 

significant bit) whichever is greater with line voltage applied.

 

DC: 120 dB (with maximum source impedance of 100 ohms) or a ±1 LSB whichever is

 

greater with 120 Vdc applied.

 

DC (to 1 KHz): 80 dB (with maximum source of impedance of 100 ohms) or ±1 LSB

 

whichever is greater with 50 Vac applied.

 

Normal Mode

 

AC (50 or 60 Hz): 60 dB (with 100 % span peak-to-peak maximum)

 

 

Digital Inputs (Two)

+30 Vdc source for external dry contacts or isolated solid state contacts. Digital Inputs are

(Optional)

isolated from line power, earth ground, analog inputs and all outputs except for the Second

 

Current Output.

 

The second Digital Input is mutually exclusive with the Second Current Output.

 

 