Specifications

Rack/battery options

The racks are deployed in multiples of two, with each rack housing one battery string. A maximum of eight racks (battery strings) can be used to support a single Symmetra MW UPS. The total number of strings deployed depends on the customer’s requirements for run-time. The racks can accommodate either Power or Fiamm battery types.

Refer to “APC Warranty on Batteries” on page 57.

Note

The following product SKUs reflect the currently available rack/battery options.

Rack SKU

Battery Type (Model)

Assembly

Qty

Wiring Style Cable Size (ref)*

 

 

 

 

 

 

SYR400k1000HxR-2CP

Power (TC-12150)

16 rails

2

E

120 mm2 (#4/0)

SYR400k1000HxR-2CF

Fiamm (12SLB130)

16 rails

2

E

120 mm2 (#4/0)

*Cobra cable rated for 150°C

Weights and dimensions

Each assembled rack measures 1778mm (H) x 1047mm (W) x 797mm (D) [70” x 41.2” x 31.4”]. For each two-rack combination, the width doubles to 2094mm [82.4”]. The weight of individual racks, battery types, and a fully loaded TWO-rack system is presented below.

Rack SKU

Weight Per Rack

Battery Type

Weight Per Batt

Total Wgt

 

 

 

 

 

SYR400k1000HxR-2CP

156 kg

Power (TC-12150)

45 kg

3192 kg

 

 

 

 

 

SYR400k1000HxR-2CF

156 kg

Fiamm (12SLB130)

42 kg

3000 kg

 

 

 

 

 