Appendix C: Employing Sidecars
2.Using one (1) 120 mm2 [#4/0] cable, connect the BAT 1- terminal in Terminal Block #1 to either of the two BAT 1- vertical bars in the Sidecar.
At Terminal Block #1: If using top cable entry, connect to top terminal (as shown) of the BAT 1- segment on right. Otherwise, connect to bottom terminal. Secure lug to stud with preset washer and nut. To relieve strain, zip tie cable to the shelf directly above the terminal block.
To BAT 1-
+-
Terminal Block #1
At the Sidecar: Connect other cable end to one of the
To BAT 1-
Battery Rack Assembly and Installation Manual | 47 |