Safety
Safety warnings
| • Only QUALIFIED ELECTRICIANS may perform this installation! Battery |
| installation must be performed in accordance with all applicable codes! |
Warning | • Observe all WARNING and CAUTION notices! Failure to do so may result in |
| SERIOUS INJURY or DEATH! |
•Disconnect charging source(s) BEFORE connecting or disconnecting battery terminals!
Electrical • Some battery terminals and other components remain LIVE even when the
Hazard
system is switched off! LETHAL VOLTAGES may still be present when the rack is
•USE EXTREME CAUTION when making terminal connections! DO NOT allow cables to touch anything except the intended terminal!
•INSULATED TOOLS and proper INSULATING MATERIALS (rubber floor stands, rubber mats, gloves, protective clothing, etc.) should be used when connecting battery cables!
Safety precautions
• Assemble racks in accordance with the instructions contained in this document
WITHOUT DEVIATION.
Caution | • For installations where grounding is required for IEC and/or local codes, see |
| |
| instructions for RACK GROUNDING. |
| • Refer to local ordinances that pertain to battery installation and storage. |
| • Handle, transport, and properly dispose of or recycle batteries in accordance |
| with regulations. |
| • |
| batteries in a |
| • Do not open, alter, or mutilate batteries! Released electrolyte is harmful to the |
| skin and eyes, and may be toxic. |
| • Batteries should always be replaced with the same number and type as |
| previously used. |
| • Batteries must remain in a |
| temperature range of 22° to 25° C [72° to 77° F] and a relative humidity of 0% |
| to 95%, |
| affect the performance of your batteries, as well as your battery warranty. |
Battery Rack Assembly and Installation Manual | 1 |