Rack Assembly

3.Using a rated lifting device, load batteries onto BOTTOM shelf rails in accordance with your wiring diagram for that shelf. Take note of where each numbered battery should be placed, and the proper positioning of its positive and negative terminals.

Because batteries are loaded from bottom-to-top in the rack, the higher- numbered batteries are placed on the lower shelves.

Prior to loading batteries, use a voltmeter to ensure each battery contains its

Note

required 12V. DO NOT load any battery with an insufficient voltage!

Leave a minimum space of 5 mm (.2 in) between batteries in the same row.

Positive Terminal

28

27

26

5 mm [.2]

5 mm [.2]

Negative Terminal

Wiring the batteries

All of the batteries loaded onto a given shelf must be connected (wired) in numerical sequence before starting assembly of the next shelf. These connections consist of battery-to-battery and row-to-row wiring.

Review “Safety” on page 1 for safety warnings and caution notices. Take heed of all safety information before proceeding with battery connections. Failure to

Warning comply could result in serious injury or death!

1.Connect all batteries in the same row (those on the same rails) using the supplied battery-to- battery cable.

Refer to your wiring diagrams for proper cabling and termination points.

Refer to instructions for “Applying cable boots” on page 19, “Connecting to batteries” on page 20, and “Covering battery connections” on page 21.

Prior to connecting batteries, use a voltmeter to check the voltage between those terminals being connected. Any reading other than zero is unacceptable.

After connecting each row, use voltmeter to measure the collective voltage.

Note

Reading should approximate number of batteries in row times 12V.