Rack Assembly

Reattaching terminal block covers

Reattach the snap-off cover to the front face of each terminal block.

Applying warning labels

Labels must be applied to the more visible areas of the racks to warn of the dangers associated with live batteries.

1.Apply supplied “Warning” Labels to the front-facing Cross Bar on each shelf in the battery racks.

2.Apply supplied “CE Rating” Label (p/n 885-1618) to a highly visible area in the vicinity of the battery installation.

Grounding the racks

Connect an external grounding cable (not supplied) to a grounding stud located in one of the rack’s Bottom Side Subassemblies. Secure the cable to the stud by applying hardware as follows: Serrated washer, Cable lug, Flange nut.

M6 Flange Nut

(803-2406)

Cable Lug

M6 Welded Grounding Stud

M6 Serrated Washer

(811-0604)

Battery Rack Assembly and Installation Manual

33