Image 50

Configuration

 

Function Prompt

 

Selection or Range of Setting

 

 

Parameter

 

Lower Display

 

Upper Display

 

 

Definition

 

English

Numeric

 

 

English

Numeric

 

 

 

 

 

Code

 

 

 

Code

 

 

 

 

 

 

 

 

 

 

 

Also defined as "HEAT" Rate on Duplex

 

 

 

 

 

 

 

 

models for variations of Heat/Cool

 

 

 

 

 

 

 

 

applications.

 

 

 

 

 

 

 

 

 

 

I MIN

103

 

 

0.02 to 50.00

 

 

I MIN = Reset in Minutes per Repeat

 

or

 

 

 

0.02 to 50.00

 

 

I RPM = Reset in Repeats per Minute

 

I RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

Integral Time (or Reset) adjusts the

 

 

 

 

 

 

 

controller's output in accordance with both

 

 

 

 

 

 

 

the size of the deviation (SP–PV) and the

 

 

 

 

 

 

 

time that it lasts. The amount of the

 

 

 

 

 

 

 

corrective action depends on the value of

 

 

 

 

 

 

 

Gain. The Reset adjustment is measured as

 

 

 

 

 

 

 

how many times proportional action is

 

 

 

 

 

 

 

repeated per minute or how many minutes

 

 

 

 

 

 

 

before one repeat of the proportional action

 

 

 

 

 

 

 

occurs.

 

 

 

 

 

 

 

Used with control algorithm PID-A or PID-B.

 

 

 

 

 

 

 

Also defined as "HEAT" Reset on Duplex

 

 

 

 

 

 

 

models for variations of Heat/Cool

 

 

 

 

 

 

 

applications.

 

 

 

 

 

 

 

 

 

The selection of whether

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

Minutes per Repeat or Repeats per Minute is

 

 

 

 

 

 

 

 

used is made in the CONTRL parameters

 

 

 

 

 

 

 

 

group under the prompt MINorRPM.

 

 

 

 

 

 

 

 

 

 

MANRST

104

 

 

-100 to 100 %

 

 

MANUAL RESET is only applicable if you

 

 

 

 

 

use control algorithm PD WITH MANUAL

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

RESET in the Algorithm Set Up group.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Because a proportional controller will not

 

 

 

 

 

 

 

 

necessarily line out at setpoint, there will be

 

 

 

 

 

 

 

 

a deviation (offset) from setpoint. This

 

 

 

 

 

 

 

 

eliminates the offset and lets the PV line out

 

 

 

 

 

 

 

 

at setpoint.

 

 

 

 

 

 

 

 

 

Bias is shown on the lower

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

display.

 

 

 

 

 

 

 

 

 

 

 

PB 2 or

105

 

 

PB = 0.1 to 1000 %

 

 

PROPORTIONAL BAND 2 or GAIN 2,

 

 

 

 

 

RATE 2, and RESET 2 parameters are the

 

GAIN 2

 

 

 

Gain = 0.01 to

 

 

 

 

 

 

 

 

same as previously described for “Heat”

 

 

 

 

1000

 

 

except that they refer to the cool zone tuning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constants on duplex models or the second

 

 

 

 

 

 

 

 

set of PID constants, whichever is pertinent.

 

 

 

 

 

 

 

 

 

 

RATE2T

106

 

 

0.00 to 10.00

 

 

This is the same as above except that it

 

 

 

 

 

applies to Duplex models for the "COOL"

 

 

 

 

 

minutes

 

 

 

 

 

 

 

 

 

zone of Heat/Cool applications or for the

 

 

 

 

 

0.08 or less = OFF

 

 

 

 

 

 

 

 

 

second set of PID constants.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

UDC2500 Universal Digital Controller Product Manual

4/07