Configuration
| Function Prompt |
| Selection or Range of Setting |
|
| Parameter | |||
| Lower Display |
| Upper Display |
|
| Definition | |||
| English | Numeric |
|
| English | Numeric |
|
|
|
|
| Code |
|
|
| Code |
|
|
|
|
|
|
|
|
|
|
| Also defined as "HEAT" Rate on Duplex | |
|
|
|
|
|
|
|
| models for variations of Heat/Cool | |
|
|
|
|
|
|
|
| applications. | |
|
|
|
|
|
|
|
|
| |
| I MIN | 103 |
|
| 0.02 to 50.00 |
|
| I MIN = Reset in Minutes per Repeat | |
| or |
|
|
| 0.02 to 50.00 |
|
| I RPM = Reset in Repeats per Minute | |
| I RPM |
|
|
|
|
| |||
|
|
|
|
|
|
|
| Integral Time (or Reset) adjusts the | |
|
|
|
|
|
|
| controller's output in accordance with both | ||
|
|
|
|
|
|
| the size of the deviation | ||
|
|
|
|
|
|
| time that it lasts. The amount of the | ||
|
|
|
|
|
|
| corrective action depends on the value of | ||
|
|
|
|
|
|
| Gain. The Reset adjustment is measured as | ||
|
|
|
|
|
|
| how many times proportional action is | ||
|
|
|
|
|
|
| repeated per minute or how many minutes | ||
|
|
|
|
|
|
| before one repeat of the proportional action | ||
|
|
|
|
|
|
| occurs. | ||
|
|
|
|
|
|
| Used with control algorithm | ||
|
|
|
|
|
|
| Also defined as "HEAT" Reset on Duplex | ||
|
|
|
|
|
|
| models for variations of Heat/Cool | ||
|
|
|
|
|
|
| applications. | ||
|
|
|
|
|
|
|
|
| The selection of whether |
|
|
|
|
|
|
|
| ATTENTION | |
|
|
|
|
|
|
|
| Minutes per Repeat or Repeats per Minute is | |
|
|
|
|
|
|
|
| used is made in the CONTRL parameters | |
|
|
|
|
|
|
|
| group under the prompt MINorRPM. | |
|
|
|
|
|
|
|
|
| |
| MANRST | 104 |
|
|
|
| MANUAL RESET is only applicable if you | ||
|
|
|
|
| use control algorithm PD WITH MANUAL | ||||
|
|
|
|
| Output |
|
| ||
|
|
|
|
|
|
| RESET in the Algorithm Set Up group. | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Because a proportional controller will not | |
|
|
|
|
|
|
|
| necessarily line out at setpoint, there will be | |
|
|
|
|
|
|
|
| a deviation (offset) from setpoint. This | |
|
|
|
|
|
|
|
| eliminates the offset and lets the PV line out | |
|
|
|
|
|
|
|
| at setpoint. | |
|
|
|
|
|
|
|
|
| Bias is shown on the lower |
|
|
|
|
|
|
|
| ATTENTION | |
|
|
|
|
|
|
|
| display. |
|
|
|
|
|
|
|
|
|
| |
| PB 2 or | 105 |
|
| PB = 0.1 to 1000 % |
|
| PROPORTIONAL BAND 2 or GAIN 2, | |
|
|
|
|
| RATE 2, and RESET 2 parameters are the | ||||
| GAIN 2 |
|
|
| Gain = 0.01 to |
|
| ||
|
|
|
|
|
| same as previously described for “Heat” | |||
|
|
|
| 1000 |
|
| except that they refer to the cool zone tuning | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| constants on duplex models or the second | |
|
|
|
|
|
|
|
| set of PID constants, whichever is pertinent. | |
|
|
|
|
|
|
|
|
| |
| RATE2T | 106 |
|
| 0.00 to 10.00 |
|
| This is the same as above except that it | |
|
|
|
|
| applies to Duplex models for the "COOL" | ||||
|
|
|
|
| minutes |
|
| ||
|
|
|
|
|
|
| zone of Heat/Cool applications or for the | ||
|
|
|
|
| 0.08 or less = OFF |
|
| ||
|
|
|
|
|
|
| second set of PID constants. | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
36 | UDC2500 Universal Digital Controller Product Manual | 4/07 |