Configuration

 

Function Prompt

 

Selection or Range of Setting

 

 

Parameter

 

Lower Display

 

Upper Display

 

 

Definition

 

English

Numeric

 

 

English

Numeric

 

 

 

 

 

 

Code

 

 

 

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

read/write.

 

 

 

 

 

CAL

1

 

 

CALIBRATION—All groups are available for

 

 

 

 

 

 

 

 

 

read/write except for the Calibration and

 

 

 

 

 

 

 

 

 

Keyboard Lockout groups.

 

 

 

 

 

CONF

2

 

 

+ CONFIGURATION—Tuning, SP Ramp,

 

 

 

 

 

 

 

 

 

and Accutune groups are read/write. All

 

 

 

 

 

 

 

 

 

other groups are read only. Calibration and

 

 

 

 

 

 

 

 

 

Keyboard Lockout groups are not available.

 

 

 

 

 

VIEW

3

 

 

+ VIEW—Tuning and Setpoint Ramp

 

 

 

 

 

 

 

 

 

parameters are read/write. No other

 

 

 

 

 

 

 

 

 

parameters are viewable.

 

 

 

 

 

ALL

4

 

 

ALL—Tuning and Setpoint Ramp

 

 

 

 

 

 

 

 

 

parameters are available for read only. No

 

 

 

 

 

 

 

 

 

other parameters are viewable.

 

 

 

 

 

 

 

 

 

 

 

AUTOMA

112

 

 

 

 

 

 

MANUAL/AUTO KEY LOCKOUT—Allows

 

 

 

 

 

 

 

you to disable the Manual/Auto key.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIS

0

 

 

DISABLE

 

 

 

 

 

ENAB

1

 

 

ENABLE

 

 

 

 

 

 

 

 

 

 

Can only be viewed if

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

LOCKOUT is

configured for NONE.

 

 

 

 

 

 

 

 

 

 

 

RN HLD

114

 

 

 

 

 

 

RUN/HOLD KEY LOCKOUT—Allows you to

 

 

 

 

 

 

 

disable the Run/Hold key, for either SP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ramp or SP Program. The Run/Hold key is

 

 

 

 

 

 

 

 

 

never disabled when used to acknowledge a

 

 

 

 

 

 

 

 

 

latched alarm 1 or a Diagnostic Message.

 

 

 

 

 

DIS

0

 

 

DISABLE

 

 

 

 

 

 

 

ENABLE

 

 

 

 

 

ENAB

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Can only be viewed if

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

LOCKOUT is

configured for NONE.

 

 

 

 

 

 

 

 

 

 

 

SP SEL

115

 

 

 

 

 

 

SETPOINT SELECT KEY LOCKOUT

 

 

 

 

 

 

 

Allows you to disable the Setpoint Select

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIS

0

 

 

key.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENAB

1

 

 

DISABLE

 

 

 

 

 

 

 

 

 

ENABLE

 

 

 

 

 

 

 

 

 

 

Can only be viewed if

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

LOCKOUT is

configured for NONE.

 

 

 

 

 

 

 

 

 

 

 

38

UDC2500 Universal Digital Controller Product Manual

4/07

Page 52