Honeywell UDC2500 manual A2S1HL, A2S1EV, A2S2TY, A2S2VA, Alhyst

Models: UDC2500

1 243
Download 243 pages 28.29 Kb
Page 94
Image 94

Configuration

 

Function Prompt

 

Selection or Range of Setting

 

 

Parameter

 

Lower Display

 

Upper Display

 

 

Definition

 

English

Numeric

 

 

English

Numeric

 

 

 

 

 

 

Code

 

 

 

Code

 

 

 

 

 

A2S1HL

1109

 

 

HIGH

0

 

 

ALARM 2 SETPOINT 1 STATE—Same as

 

 

 

 

 

A1S1HL.

 

 

 

 

 

LOW

1

 

 

 

 

 

 

 

 

 

 

 

 

A2S1EV

1109

 

 

BEGIN

0

 

 

ALARM 2 SEGMENT EVENT 1—Same as

 

 

 

 

 

END

1

 

 

A1S1EV.

 

 

 

 

 

 

 

 

 

 

 

A2S2TY

1110

 

 

 

 

 

 

ALARM 2 SETPOINT 2 TYPE—Select what

 

 

 

 

 

 

 

 

 

you want Setpoint 2 of Alarm 2 to represent.

 

 

 

 

 

 

 

 

 

The selections are the same as A1S1TYPE.

 

 

 

 

 

 

 

 

 

 

Not applicable with Relay

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

Duplex unless

using Dual Relay PWA.

 

 

 

 

 

 

 

 

 

 

 

A2S2VA

1111

 

 

Value in

 

 

 

ALARM 2 SETPOINT 2 VALUE—This is the

 

 

 

 

 

engineering units

 

 

 

value at which you want the alarm type

 

 

 

 

 

 

 

 

 

chosen in prompt A2S2TYPE to actuate.

 

 

 

 

 

 

 

 

 

The details are the same as A1S1 VAL.

 

 

 

 

 

 

 

 

 

 

 

A2S1HL

1112

 

 

HIGH

0

 

 

ALARM 2 SETPOINT 1 STATE—Same as

 

 

 

 

 

A1S1HL.

 

 

 

 

 

LOW

1

 

 

 

 

 

 

 

 

 

 

 

 

A2S1EV

1112

 

 

BEGIN

0

 

 

ALARM 2 SEGMENT EVENT 2—Same as

 

 

 

 

 

END

1

 

 

A1S1EV.

 

 

 

 

 

 

 

 

 

 

 

ALHYST

1113

 

 

0.0 to 100.0 % of

 

 

 

ALARM HYSTERESIS—A single adjustable

 

 

 

 

 

span or full output

 

 

 

hysteresis is provided on alarms such that

 

 

 

 

 

as appropriate

 

 

 

when the alarm is OFF it activates at exactly

 

 

 

 

 

 

 

 

 

the alarm setpoint; when the alarm is ON, it

 

 

 

 

 

 

 

 

 

will not deactivate until the variable is 0.0 %

 

 

 

 

 

 

 

 

 

to 100 % away from the alarm setpoint.

 

 

 

 

 

 

 

 

 

Configure the hysteresis of the alarms based

 

 

 

 

 

 

 

 

 

on INPUT signals as a % of input range

 

 

 

 

 

 

 

 

 

span.

 

 

 

 

 

 

 

 

 

Configure the hysteresis of the alarm based

 

 

 

 

 

 

 

 

 

on OUTPUT signals as a % of the full scale

 

 

 

 

 

 

 

 

 

output range.

 

 

 

 

 

 

 

 

 

 

 

80

UDC2500 Universal Digital Controller Product Manual

4/07

Page 94
Image 94
Honeywell UDC2500 manual A2S1HL, A2S1EV, A2S2TY, A2S2VA, Alhyst