Configuration

 

Function Prompt

 

Selection or Range of Setting

 

 

Parameter

 

Lower Display

 

Upper Display

 

 

Definition

 

English

Numeric

 

 

English

Numeric

 

 

 

 

 

 

Code

 

 

 

Code

 

 

 

 

 

A2S1HL

1109

 

 

HIGH

0

 

 

ALARM 2 SETPOINT 1 STATE—Same as

 

 

 

 

 

A1S1HL.

 

 

 

 

 

LOW

1

 

 

 

 

 

 

 

 

 

 

 

 

A2S1EV

1109

 

 

BEGIN

0

 

 

ALARM 2 SEGMENT EVENT 1—Same as

 

 

 

 

 

END

1

 

 

A1S1EV.

 

 

 

 

 

 

 

 

 

 

 

A2S2TY

1110

 

 

 

 

 

 

ALARM 2 SETPOINT 2 TYPE—Select what

 

 

 

 

 

 

 

 

 

you want Setpoint 2 of Alarm 2 to represent.

 

 

 

 

 

 

 

 

 

The selections are the same as A1S1TYPE.

 

 

 

 

 

 

 

 

 

 

Not applicable with Relay

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

Duplex unless

using Dual Relay PWA.

 

 

 

 

 

 

 

 

 

 

 

A2S2VA

1111

 

 

Value in

 

 

 

ALARM 2 SETPOINT 2 VALUE—This is the

 

 

 

 

 

engineering units

 

 

 

value at which you want the alarm type

 

 

 

 

 

 

 

 

 

chosen in prompt A2S2TYPE to actuate.

 

 

 

 

 

 

 

 

 

The details are the same as A1S1 VAL.

 

 

 

 

 

 

 

 

 

 

 

A2S1HL

1112

 

 

HIGH

0

 

 

ALARM 2 SETPOINT 1 STATE—Same as

 

 

 

 

 

A1S1HL.

 

 

 

 

 

LOW

1

 

 

 

 

 

 

 

 

 

 

 

 

A2S1EV

1112

 

 

BEGIN

0

 

 

ALARM 2 SEGMENT EVENT 2—Same as

 

 

 

 

 

END

1

 

 

A1S1EV.

 

 

 

 

 

 

 

 

 

 

 

ALHYST

1113

 

 

0.0 to 100.0 % of

 

 

 

ALARM HYSTERESIS—A single adjustable

 

 

 

 

 

span or full output

 

 

 

hysteresis is provided on alarms such that

 

 

 

 

 

as appropriate

 

 

 

when the alarm is OFF it activates at exactly

 

 

 

 

 

 

 

 

 

the alarm setpoint; when the alarm is ON, it

 

 

 

 

 

 

 

 

 

will not deactivate until the variable is 0.0 %

 

 

 

 

 

 

 

 

 

to 100 % away from the alarm setpoint.

 

 

 

 

 

 

 

 

 

Configure the hysteresis of the alarms based

 

 

 

 

 

 

 

 

 

on INPUT signals as a % of input range

 

 

 

 

 

 

 

 

 

span.

 

 

 

 

 

 

 

 

 

Configure the hysteresis of the alarm based

 

 

 

 

 

 

 

 

 

on OUTPUT signals as a % of the full scale

 

 

 

 

 

 

 

 

 

output range.

 

 

 

 

 

 

 

 

 

 

 