Configuration

 

Function Prompt

Selection or Range of Setting

 

 

Parameter

 

Lower Display

Upper Display

 

 

Definition

 

English

Numeric

 

English

 

Numeric

 

 

 

 

 

 

Code

 

 

 

Code

 

 

 

 

 

 

 

 

CUR

2

 

 

CURRENT SIMPLEX—Type of output using

 

 

 

 

 

 

 

 

one 4 mA to 20 mA signal that can be fed

 

 

 

 

 

 

 

 

 

into a positive or negative grounded load of 0

 

 

 

 

 

 

 

 

 

to 1000 ohms. This signal can easily be

 

 

 

 

 

 

 

 

 

configured for 4-20 mA or 0-20 mA operation

 

 

 

 

 

 

 

 

 

via the CRANGE configuration, below.

 

 

 

 

RLYD

3

 

 

TIME DUPLEX—This output algorithm uses

 

 

 

 

 

 

 

 

Digital Outputs 1 and 2 for Duplex Time

 

 

 

 

 

 

 

 

 

Proportional Control. The outputs are

 

 

 

 

 

 

 

 

 

updated per the Loop sampling rate

 

 

 

 

 

 

 

 

 

selection. Time Proportional Output has a

 

 

 

 

 

 

 

 

 

resolution of 4.44 msec. Cycle Time is

 

 

 

 

 

 

 

 

 

adjustable from 1 second to 120 seconds.

 

 

 

 

CURD

4

 

 

CURRENT DUPLEX is similar to current

 

 

 

 

 

 

 

 

simplex but uses a second current output.

 

 

 

 

 

 

 

 

 

The second output is usually scaled so that

 

 

 

 

 

 

 

 

 

zero and span correspond with 0 % and

 

 

 

 

 

 

 

 

 

50 % output (cool zone). When the output is

 

 

 

 

 

 

 

 

 

0 % to 50 %, the controller uses tuning

 

 

 

 

 

 

 

 

 

parameter set #2, when the output is 50 % to

 

 

 

 

 

 

 

 

 

100 % it uses set #1.

 

 

 

 

 

 

 

 

 

 

Other prompts affected: 4-20

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

RNG

 

 

 

 

 

CURT

5

 

 

CURRENT/TIME DUPLEX is a variation of

 

 

 

 

 

 

 

 

duplex with current active for 0 % to 50 %

 

 

 

 

 

 

 

 

 

output (tuning set 2) and time is active 50 %

 

 

 

 

 

 

 

 

 

to 100 % output (tuning set 1).

 

 

 

 

 

 

 

 

 

Relay controls heat, current controls cool.

 

 

 

 

 

 

 

 

 

 

Other prompts affected: 4-20

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

RNG

 

 

 

 

 

TCUR

6

 

 

TIME CURRENT DUPLEX is similar to CUR

 

 

 

 

 

 

 

 

TI except that current is active for 50 % to

 

 

 

 

 

 

 

 

 

100 % and time is active for 0 % to 50 %.

 

 

 

 

 

 

 

 

 

Relay controls cool, current controls heat.

 

 

 

 

 

 

 

 

 

 

Other prompts affected: 4-20

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

RNG

 

 

 

 

 

 

 

 

 

 

 

 

CRANGE

502

 

4-20

 

0

 

 

CURRENT OUTPUT RANGE allows the

 

 

 

 

 

user to easily select 4-20 mA output or 0-20

 

 

 

 

0-20

 

1

 

 

 

 

 

 

 

 

 

mA output operation without the need for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recalibration of the instrument.

 

 

 

 

 

 

 

 

 

 

 

OUTRNG

504

 

 

 

 

 

 

CURRENT DUPLEX RANGE ALGORITHM

 

 

 

 

 

 

 

— Used with Output Algorithm selections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURD, CURT, or TCUR.

 

 

 

 

 

 

 

 

 

 

 

52

UDC2500 Universal Digital Controller Product Manual

4/07

Page 66
Image 66
Honeywell UDC2500 manual Crange, Outrng, Current Duplex Range Algorithm