Honeywell UDC2500 manual Input #1, Rtd

Models: UDC2500

1 243
Download 243 pages 28.29 Kb
Page 37
Image 37

Installation

Input #1

Thermocouple

RTD

Millivolt or Volts

except 0-10 Volts

 

 

Use Thermocouple extension wire only

25

R

3

 

26

+

27

25 R

26 + 27 –

25 R

mV or

+

26 +

Volt

 

 

source

27 –

0-10 Volts

Milliamps

Thermocouple Differential

0–10 Volt source

+

1

100K 1

2

100K 3

25 R

26 + 27 –

25 R

Xmitter

1

 

 

+

 

26

+

250

 

Ω

 

 

 

 

 

Power

 

 

27 –

 

+ –

 

 

Supply

 

 

 

 

Use Thermocouple

 

 

extension wire only

25

R

+

 

 

 

 

4

26

+

2

 

 

27

 

+

 

 

 

1The 250 ohm resistor for milliamp inputs or the voltage divider for 0-10 Volt inputs are supplied with the controller when those inputs are specified. These items must be installed prior to start up when the controller is wired. For 0-20 mA applications, the resistor should be located at the transmitter terminals if Burnout detection is desired.

2Splice and tape this junction between the two thermocouples. This junction may be located anywhere between the thermocouples and the instrument terminals, it does not need to be close to the other thermocouple junctions. Both thermocouples must be of the same type. For best accuracy, the two thermocouples should be matched or, preferably, made from the same batch of wire.

3This controller does not produce a steady current for burnout detection. For that reason, when a thermocouple is used in parallel with another instrument, it may be desirable to configure the burnout selection for this controller to “NOFS” and use the burnout current from the other instrument to also drive this controller.

4The millivolt values for the Thermocouple Differential Input are for a pair of J thermocouples at an ambient temperature mean of 450°F / 232°C.

Figure 2-6 Input 1 Connections

4/07

UDC2500 Universal Digital Controller Product Manual

23

Page 37
Image 37
Honeywell UDC2500 manual Input #1, Rtd