Troubleshooting/Service
7.8 Restoring Factory Configuration
Introduction
This procedure restores the configuration of the instrument back to the Factory Settings per Section 3.17.
ATTENTION: Restoring the factory configuration overwrites all
Table
Table 7-15 Restoring Factory Configuration
Step | What to do |
|
|
1Turn off the power to the instrument for at least five seconds.
2Turn the power back on and simultaneously press the “FUNCTION” and keys. This must be done while “TEST DONE” is being displayed.
3If step 2 was performed correctly, the instrument will now display “UDC” [Upper] “UPDATE” [Lower].
4
5
Press the FUNCTION Key. The instrument will now display “DIS” [Upper] “RESTORE” [Lower].
Press the key. The instrument will now display “CFG” [Upper] “RESTORE” [Lower].
6Press the FUNCTION Key. The instrument will now display “DOIN” “RESTORE”
7When the instrument finishes the restore operation, it automatically resets itself and restarts in the product mode. The instrument configuration will now be the same as it was when the instrument left the factory and all user- entered configurations since that time have been overwritten.