Environmental and Operating Conditions

Parameter

 

Reference

Rated

Operative

Transportation and

 

 

 

 

Limits

Storage

 

 

 

 

 

 

Ambient Temperature

25

± 3 °C

15 to 55 °C

0 to 55 °C

–40 to 66 °C

 

77

± 5 °F

58 to 131 °F

32 to 131 °F

–40 to 151 °F

Relative Humidity

10 to 55*

10 to 90*

5 to 90*

5 to 95*

 

 

 

 

 

 

Vibration

0

 

0 to 70

0 to 200

0 to 200

Frequency (Hz)

 

Acceleration (g)

0

 

0.4

0.6

0.5

 

 

 

 

 

 

Mechanical Shock

0

 

1

5

20

Acceleration (g)

 

Duration (ms))

0

 

30

30

30

 

 

 

 

 

Line Voltage (Vdc)

+24 ± 1

22 to 27

20 to 27

- -

 

 

 

 

 

 

Line Voltage (Vac)

120 ± 1

90 to 240

90 to 264

- -

90 to 240 Vac

 

240 ± 2

 

 

- -

24 Vac

24

± 1

20 to 27

20 to 27

- -

 

 

 

 

 

 

Frequency (Hz)

50

± 0.2

49 to 51

48 to 52

- -

(For Vac)

60

± 0.2

59 to 61

58 to 62

- -

 

 

 

 

 

 

*The maximum moisture rating only applies up to 40 °C (104 °F). For higher temperatures, the RH specification is derated to maintain constant moisture content.