| Configuration |
|
|
|
|
|
|
|
|
| |
| Function Prompt | Selection or Range of Setting |
|
| Parameter | |||
| Lower Display | Upper Display |
|
| Definition | |||
| English | Numeric | English | Numeric |
|
|
|
|
|
| Code |
| Code |
|
|
|
|
| OUT Hi | 811 |
|
|
| HIGH OUTPUT | ||
|
|
|
|
|
| value of output beyond which you do not | ||
|
|
|
|
|
| want the controller automatic output to | ||
|
|
|
|
|
| exceed. | ||
|
|
| 0 % to 100 % |
|
| For relay output types. | ||
|
|
|
|
| For current output types. | |||
| OUT Lo | 812 |
|
|
| LOW OUTPUT | ||
|
|
|
|
|
| value of output below which you do not want | ||
|
|
|
|
|
| the controller automatic output to exceed. | ||
|
|
| 0 % to 100 % |
|
| For relay output types. | ||
|
|
|
|
| For current output types. | |||
|
|
|
|
|
|
|
| |
| D BAND | 813 |
|
|
| DEADBAND is an adjustable gap between | ||
|
|
|
|
|
| the operating ranges of output 1 and output 2 | ||
|
|
|
|
|
| in which neither output operates (positive | ||
|
|
|
|
|
| value) or both outputs operate (negative | ||
|
|
|
|
|
| value). | ||
|
|
|
|
| Time Duplex | |||
|
|
| 0.0 to 25.0 % |
|
| |||
|
|
| 0.5 to 5.0 % |
|
| Three Position Step | ||
|
|
|
|
|
|
| ||
| HYST | 814 | 0.0 to 100.0 % of |
|
| HYSTERESIS (OUTPUT RELAY) is an | ||
|
|
| PV |
|
| adjustable overlap of the ON/OFF states of | ||
|
|
|
|
|
| each control output. This is the difference | ||
|
|
|
|
|
| between the value of the process variable at | ||
|
|
|
|
|
| which the control outputs energize and the | ||
|
|
|
|
|
| value at which they | ||
|
|
|
|
|
|
| Only applicable for ON/OFF | |
|
|
|
|
|
| ATTENTION | ||
|
|
|
|
|
| control. |
| |
|
|
|
|
|
|
| ||
| FAILSF | 815 | 0 to 100 % |
|
| FAILSAFE OUTPUT | ||
|
|
|
|
|
| used here will also be the output level when | ||
|
|
|
|
|
| you have Communications SHED set to | ||
|
|
|
|
|
| failsafe or when NO BURNOUT is configured | ||
|
|
|
|
|
| and Input 1 fails. | ||
|
|
|
|
|
|
| Applies for all output types | |
|
|
|
|
|
| ATTENTION | ||
|
|
|
|
|
| except Three | Position Step Control. | |
|
|
|
|
|
|
| ||
| FAILSF | 816 |
|
|
| THREE POSITION STEP FAILSAFE | ||
|
|
|
|
|
| OUTPUT | ||
|
|
| 0 |
|
| 0 | ||
|
|
| 100 |
|
| 100 | ||
|
|
|
|
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 65 |