Input Calibration

5.8 Restore Input Factory Calibration

Introduction

The factory calibration constants for all the input actuation types that can be used with the controller are stored in its non-volatile memory. Thus, you can quickly restore the “Factory Calibration” for a given input actuation type by simply changing the actuation type to another type and then changing it back to the original type.

Refer to Table 5-14 Restore Factory Calibration for procedure

ATTENTION

A restored factory calibration overwrites any previous field calibration done for the input and may change the High and Low Range Limits.

Protect your field calibration from accidental overwrites by configuring the appropriate LOCKOUT selection after calibration.

See Section 3 - Configuration for specific instructions to set the lockout.

Table 5-14 Restore Factory Calibration

Step

Operation

Press

Result

1Set LOCKOUT to

NONE

Setup

until you see:

Upper Display = SET UP Lower Display = TUNING

Function

Until you see:

Upper Display = one of the following: NONE – all parameters are read/write

CAL – all parameters are read/write except Calibration CONF – configuration parameters are Read Only; no writes permitted

VIEW – Tuning and Setpoint Ramp parameters are read/write. No other parameters can be viewed.

ALL – Tuning and Setpoint Ramp parameters are available for read only. No other parameters can be viewed.

Lower Display = LOCK

 

 

or

2

Enter INPUT 1

Setup

 

Setup Group

 

 

 

 

Function

 

 

or

3Scroll through

FunctionsFunction

Until NONE is in the upper display

until you see:

Upper Display = SET UP

Lower Display = INPUT 1 or 2

until you see:

Upper Display = the current selection

Lower Display = INxTYP

to change the current selection to another selection

until the lower display rolls through the rest of the functions and returns to:

Upper Display = the new selection

Lower Display = INxTYP

4/07

UDC2500 Universal Digital Controller Product Manual

149

Page 163
Image 163
Honeywell UDC2500 manual Restore Input Factory Calibration, Restore Factory Calibration