Configuration

Function Prompt

Selection or Range of Setting

 

 

Parameter

Lower Display

 

Upper Display

 

 

Definition

English

Numeric

 

English

Numeric

 

 

 

 

Code

 

 

Code

 

 

 

 

 

2 PR

 

2

 

TWO SETS PV AUTOMATIC

 

 

 

 

 

 

SWITCHOVER—When the process variable

 

 

 

 

 

 

is GREATER than the value set at prompt

 

 

 

 

 

 

SW VALUE (Switchover Value), the

 

 

 

 

 

 

controller will use Gain, Rate, Reset, and

 

 

 

 

 

 

Cycle Time. The active PID SET can be read

 

 

 

 

 

 

in the lower display.

 

 

 

 

 

 

When the process variable is LESS than the

 

 

 

 

 

 

value set at prompt SW VALUE, the

 

 

 

 

 

 

controller will use Gain #2, Rate #2, Reset

 

 

 

 

 

 

#2, and Cycle #2 Time. The active PID SET

 

 

 

 

 

 

can be read in the lower display.

 

 

 

 

 

 

 

Other prompts affected: SW

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

VALUE

 

 

 

2 SP

 

3

 

TWO SETS SP AUTOMATIC

 

 

 

 

 

 

SWITCHOVER—When the setpoint is

 

 

 

 

 

 

GREATER than the value set at prompt SW

 

 

 

 

 

 

VALUE (Switchover Value), the controller will

 

 

 

 

 

 

use Gain, Rate, Reset, and Cycle.

 

 

 

 

 

 

When the setpoint is LESS than the value

 

 

 

 

 

 

set at prompt SW VALUE, the controller will

 

 

 

 

 

 

use Gain #2, Rate #2, Reset #2, and Cycle

 

 

 

 

 

#2.

 

 

 

 

 

 

 

 

Other prompts affected: SW

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

VALUE

 

 

 

 

 

 

 

SW VAL

802

Value in

 

 

AUTOMATIC SWITCHOVER VALUE—This

 

 

engineering units

 

 

is the value of Process Variable or Setpoint

 

 

within PV or SP

 

 

at which the controller will switch from

 

 

range limits

 

 

Tuning Constant Set #2 to Set #1.

 

 

 

 

 

 

 

Only appears when PID

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

SETS selection

is configured for either 2

 

 

 

 

 

 

PVSW or 2 SPSW.

 

 

 

 

 

 

 

LSP’S

803

 

 

 

 

LOCAL SETPOINT SOURCE—This

 

 

 

 

 

 

selection determines what your local setpoint

 

 

 

 

 

 

source will be.

 

 

ONE

 

0

 

LOCAL SETPOINT—The setpoint entered

 

 

 

 

 

 

from the keyboard.

 

 

 

 

 

 

 

 

62

UDC2500 Universal Digital Controller Product Manual

4/07

Page 76
Image 76
Honeywell UDC2500 manual TWO Sets PV Automatic, TWO Sets SP Automatic, Sw Val, Lsp’S