Modbus Read, Write and Override Parameters plus Exception Codes

10.7.5Output Algorithms

Table 10-13lists all the register addresses and ranges or selections for the function parameters in Set-up Group Output.

Table 10-13 Set-up Group – Output

Parameter

Register

Data

Access

 

Data Range or

Description

Address

Type

 

 

Enumerated Selection

 

 

 

 

 

 

 

 

Hex

Decimal

 

 

 

 

 

 

 

 

 

 

 

Output

00A0

160

INT

R/W

0

= Time Simplex

Algorithm

 

 

 

 

1

= Not Used

 

 

 

 

 

2

= Current Simplex

 

 

 

 

 

3

= Three Position Step or

 

 

 

 

 

 

Position Proportioning

 

 

 

 

 

4

= Time Duplex

 

 

 

 

 

5

= Current Duplex

 

 

 

 

 

6

= Current/Time Duplex

 

 

 

 

 

7

= Time/Current Duplex

Relay Cycle

00BE

190

INT

R/W

0

= 1 second increments

Time

 

 

 

 

1

= 1/3 second increments

Increments

 

 

 

 

 

 

 

 

 

 

 

 

Motor Time for

004B

075

INT

R/W

5 to 1800 seconds

Three Position

 

 

 

 

 

 

Step

 

 

 

 

 

 

 

 

 

 

 

 

 

Current Range

0099

153

INT

R/W

0

= Full (100%)

for Current

 

 

 

 

1

= Split (50%)

Duplex

 

 

 

 

 

 

 

 

 

 

 

 

 

Current Output

00EA

235

INT

R/W

0

= 4-20 mA

Range

 

 

 

 

1

= 0-20 mA

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

203

Page 217
Image 217
Honeywell UDC2500 manual Output Algorithms, Set-up Group Output