Modbus Read, Write and Override Parameters plus Exception Codes

Parameter

Register

Data

Access

 

Data Range or

Description

Address

Type

 

 

Enumerated Selection

 

Hex

Decimal

 

 

 

 

High Output

000E

014

FP

R/W

–5 to 105% of output

Limit

 

 

 

 

 

 

Low Output

000F

015

FP

R/W

–5 to 105% of output

Limit

 

 

 

 

 

 

Output Deadband

0012

018

FP

R/W

–5 to +25.0%

for Time Duplex

 

 

 

 

 

 

Output Deadband

0014

020

FP

R/W

0.5 to 5.0%

for TPSC

 

 

 

 

 

 

Output

0013

019

FP

R/W

0.0 to 100.0% of PV

Hysteresis

 

 

 

 

 

 

Failsafe Mode

00D5

213

INT

R/W

0

= Latching

 

 

 

 

 

1

= Non latching

Failsafe Output

0028

040

FP

R/W

0 to 100%

Level

 

 

 

 

 

 

TPSC Power-up

00B7

183

INT

R/W

0

= Last

Output

 

 

 

 

1

= Failsafe

TPSC Failsafe

00B8

184

INT

R/W

0

= Motor goes to closed

Output

 

 

 

 

 

position (0%)

 

 

 

 

 

1

= Motor goes to open

 

 

 

 

 

 

position (100%)

Proportional

0094

148

INT

R/W

0

= Gain

Band Units

 

 

 

 

1

= Proportional band

Reset Units

0095

149

INT

R/W

0

= Minutes

 

 

 

 

 

1

= RPM

PV High Range

0036

054

FP

R

PV High Limit

 

 

 

 

 

 

PV Low Range

0037

055

FP

R

PV Low Limit

 

 

 

 

 

 

 

210

UDC2500 Universal Digital Controller Product Manual

4/07

Page 224
Image 224