Modbus Read, Write and Override Parameters plus Exception Codes
Parameter | Register | Data | Access |
| Data Range or | |
Description | Address | Type |
|
| Enumerated Selection | |
| Hex | Decimal |
|
|
|
|
High Output | 000E | 014 | FP | R/W | ||
Limit |
|
|
|
|
|
|
Low Output | 000F | 015 | FP | R/W | ||
Limit |
|
|
|
|
|
|
Output Deadband | 0012 | 018 | FP | R/W | ||
for Time Duplex |
|
|
|
|
|
|
Output Deadband | 0014 | 020 | FP | R/W | 0.5 to 5.0% | |
for TPSC |
|
|
|
|
|
|
Output | 0013 | 019 | FP | R/W | 0.0 to 100.0% of PV | |
Hysteresis |
|
|
|
|
|
|
Failsafe Mode | 00D5 | 213 | INT | R/W | 0 | = Latching |
|
|
|
|
| 1 | = Non latching |
Failsafe Output | 0028 | 040 | FP | R/W | 0 to 100% | |
Level |
|
|
|
|
|
|
TPSC | 00B7 | 183 | INT | R/W | 0 | = Last |
Output |
|
|
|
| 1 | = Failsafe |
TPSC Failsafe | 00B8 | 184 | INT | R/W | 0 | = Motor goes to closed |
Output |
|
|
|
|
| position (0%) |
|
|
|
|
| 1 | = Motor goes to open |
|
|
|
|
|
| position (100%) |
Proportional | 0094 | 148 | INT | R/W | 0 | = Gain |
Band Units |
|
|
|
| 1 | = Proportional band |
Reset Units | 0095 | 149 | INT | R/W | 0 | = Minutes |
|
|
|
|
| 1 | = RPM |
PV High Range | 0036 | 054 | FP | R | PV High Limit | |
|
|
|
|
|
| |
PV Low Range | 0037 | 055 | FP | R | PV Low Limit | |
|
|
|
|
|
|
|
210 | UDC2500 Universal Digital Controller Product Manual | 4/07 |