Modbus Read, Write and Override Parameters plus Exception Codes
10.7 Configuration Parameters
Overview
Listed on the next pages are the identifying codes for the parameters in the various
Reading or Writing
Do a Read or Write, depending on your requirements, using the identifying code and format code listed in the tables. The range or selection available for each range is listed in the tables.
10.7.1Tuning
Table
|
| Table | |||
Parameter | Register | Data | Access | Data Range or | |
Description | Address | Type |
| Enumerated Selection | |
| Hex | Decimal |
|
|
|
|
|
|
|
|
|
Gain #1 or PB | 0001 | 001 | FP | R/W | 0.01 to 1000 Gain |
Note 1 |
|
|
|
| 0.1 to 1000 PB |
|
|
|
|
|
|
Rate #1 | 0002 | 002 | FP | R/W | 0.00 to 10.00 |
Note 1 |
|
|
|
|
|
|
|
|
|
|
|
Reset #1 | 0003 | 003 | FP | R/W | 0.02 to 50.00 |
Note 1 |
|
|
|
|
|
|
|
|
|
|
|
Manual Reset | 000D | 013 | FP | R/W | |
|
|
|
|
|
|
Gain #2 or PB #2 | 0004 | 004 | FP | R/W | 0.01 to 1000 Gain |
Note 1 |
|
|
|
| 0.1 to 1000 PB |
|
|
|
|
|
|
Rate #2 | 0005 | 005 | FP | R/W | 0.00 to 10.00 |
Note 1 |
|
|
|
|
|
|
|
|
|
|
|
Reset #2 | 0006 | 006 | FP | R/W | 0.02 to 50.00 |
Note 1 |
|
|
|
|
|
|
|
|
|
|
|
Cycle Time #1 | 15 | 21 | INT | R/W | 1 to 120 seconds |
|
|
|
|
|
|
Cycle Time #2 | 16 | 22 | INT | R/W | 1 to 120 seconds |
|
|
|
|
|
|