Honeywell UDC2500 manual Alarm Outputs

Models: UDC2500

1 243
Download 243 pages 28.29 Kb
Page 23
Image 23

 

 

Installation

 

 

 

 

 

 

 

Specifications

 

Controller Output

Electromechanical Relays (One or Two)

 

Types

SPDT contacts. Both Normally Open and Normally Closed contacts are brought out to the

 

 

 

rear terminals. Internally socketed.

 

 

 

Resistive Load: 5 amps @ 120 Vac or 240 Vac or 30 Vdc

 

 

 

Inductive Load (cosϕ = 0.4): 3 amps @ 130 Vac or 250 Vac

 

 

 

Inductive Load (L/R = 7 msec): 3.5 amps @ 30 Vdc

 

 

 

Motor: 1/6 H.P.

 

 

 

Dual Electromechanical Relays

 

 

 

Two SPST contacts. One Normally Closed contact for each relay is brought out to the rear

 

 

 

terminals. Useful for Time Duplex or Three Position Step control applications, this option

 

 

 

takes the place of one of the above electromechanical relays, thus saving it for use as an

 

 

 

alarm. Units with this output option may have two additional relays (total of four relays) plus

 

 

 

the Second Current Output. Relays are internally socketed.

 

 

 

Resistive Load: 2 amps @ 120 Vac, 240 Vac or 30 Vdc

 

 

 

Inductive Load (cosϕ = 0.4): 1 amp @ 130 Vac or 250 Vac

 

 

 

Inductive Load (L/R = 7 msec): 1 amp @ 30 Vdc

 

 

 

Solid State Relays (One or Two)

 

 

 

Zero-crossing type SPST solid state contacts consisting of a triac N.O. output. Internally

 

 

 

socketed.

 

 

 

Resistive Load: 1.0 amp @ 25°C and 120 or 240 Vac, 0.5 amp @ 55°C and 120 or 240 Vac

 

 

 

Inductive Load: 50 VA @ 120 Vac or 240 Vac

 

 

 

Minimum Load: 20 milliamps

 

 

 

Open Collector Outputs (One or Two)

 

 

 

Socketed assembly replacing a relay. Opto-isolated from all other circuits except current

 

 

 

output and not from each other. Internally powered @ 30 Vdc.

 

 

 

Note: Applying an external power supply to this output will damage the instrument.

 

 

 

Maximum Sink Current: 20 mA

 

 

 

Short-circuit current limit: 100 mA

 

 

 

Current Outputs (One or Two)

 

 

 

These outputs provide a 21 mA dc maximum into a negative or positive grounded load or into

 

 

 

a non-grounded load. Current outputs are isolated from each other, line power, earth ground

 

 

 

and all inputs. Outputs can be easily configured via the keyboard for either direct or reverse

 

 

 

action and for either 0 to 20 mA or 4 to 20 mA without field calibration.

 

 

 

The second current output can be used in an Auxiliary Output mode. This Auxiliary Output

 

 

 

can be configured to represent either Input, PV, Setpoint, Deviation, or Control output. The

 

 

 

range of an Auxiliary Output can be scaled per the range of the selected variable and can be

 

 

 

set anywhere between 0 to 21 mA. The Second Current Output is mutually exclusive with the

 

 

 

second Digital Input.

 

 

 

Resolution: 12 bits over 0 to 21 mA

 

 

 

Accuracy: 0.05% of full scale

 

 

 

Temperature Stability: 0.01% F.S./°C

 

 

 

Load Resistance: 0 to 1000 ohms

 

 

 

 

Alarm Outputs

One SPDT Electromechanical relay. A second alarm is available if the second control relay

 

(Optional)

is not used for control purposes or when the Dual Relay Option is used.

 

 

 

Up to four setpoints are independently set as high or low alarm, two for each relay. Setpoint

 

 

 

can be on any Input, Process Variable, Deviation, Manual Mode, Failsafe, PV Rate, RSP

 

 

 

Mode, Communication Shed, or Output. A single adjustable hysteresis of 0.0 to 100.0% is

 

 

 

provided. The alarm can also be set as an ON or OFF event at the beginning of a Setpoint

 

 

 

ramp/soak segment.

 

 

 

Alarm Relay Contacts Rating: Resistive Load: 5 amps at 120 Vac or 240 Vac or 30 Vdc

 

 

 

 

Isolation (Functional)

Analog Inputs: are isolated from all other circuits at 850Vdc for 2 seconds, but not from each

 

 

 

other.

 

 

 

Analog Outputs: are isolated from all other circuits at 850Vdc for 2 seconds.

 

 

 

AC Power: is electrically isolated from all other inputs and outputs to withstand a HIPOT

 

 

 

potential of 1900Vdc for 2 seconds per Annex K of EN61010-1.

 

 

 

Relay Contacts: with a working voltage of 115/230 Vac, are isolated from each other and all

 

 

 

other circuits at 345Vdc for 2 seconds.

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

9