| Installation |
|
|
|
|
|
|
| Specifications |
|
Controller Output | Electromechanical Relays (One or Two) |
| |
Types | SPDT contacts. Both Normally Open and Normally Closed contacts are brought out to the |
| |
|
| rear terminals. Internally socketed. |
|
|
| Resistive Load: 5 amps @ 120 Vac or 240 Vac or 30 Vdc |
|
|
| Inductive Load (cosϕ = 0.4): 3 amps @ 130 Vac or 250 Vac |
|
|
| Inductive Load (L/R = 7 msec): 3.5 amps @ 30 Vdc |
|
|
| Motor: 1/6 H.P. |
|
|
| Dual Electromechanical Relays |
|
|
| Two SPST contacts. One Normally Closed contact for each relay is brought out to the rear |
|
|
| terminals. Useful for Time Duplex or Three Position Step control applications, this option |
|
|
| takes the place of one of the above electromechanical relays, thus saving it for use as an |
|
|
| alarm. Units with this output option may have two additional relays (total of four relays) plus |
|
|
| the Second Current Output. Relays are internally socketed. |
|
|
| Resistive Load: 2 amps @ 120 Vac, 240 Vac or 30 Vdc |
|
|
| Inductive Load (cosϕ = 0.4): 1 amp @ 130 Vac or 250 Vac |
|
|
| Inductive Load (L/R = 7 msec): 1 amp @ 30 Vdc |
|
|
| Solid State Relays (One or Two) |
|
|
|
| |
|
| socketed. |
|
|
| Resistive Load: 1.0 amp @ 25°C and 120 or 240 Vac, 0.5 amp @ 55°C and 120 or 240 Vac |
|
|
| Inductive Load: 50 VA @ 120 Vac or 240 Vac |
|
|
| Minimum Load: 20 milliamps |
|
|
| Open Collector Outputs (One or Two) |
|
|
| Socketed assembly replacing a relay. |
|
|
| output and not from each other. Internally powered @ 30 Vdc. |
|
|
| Note: Applying an external power supply to this output will damage the instrument. |
|
|
| Maximum Sink Current: 20 mA |
|
|
|
| |
|
| Current Outputs (One or Two) |
|
|
| These outputs provide a 21 mA dc maximum into a negative or positive grounded load or into |
|
|
| a |
|
|
| and all inputs. Outputs can be easily configured via the keyboard for either direct or reverse |
|
|
| action and for either 0 to 20 mA or 4 to 20 mA without field calibration. |
|
|
| The second current output can be used in an Auxiliary Output mode. This Auxiliary Output |
|
|
| can be configured to represent either Input, PV, Setpoint, Deviation, or Control output. The |
|
|
| range of an Auxiliary Output can be scaled per the range of the selected variable and can be |
|
|
| set anywhere between 0 to 21 mA. The Second Current Output is mutually exclusive with the |
|
|
| second Digital Input. |
|
|
| Resolution: 12 bits over 0 to 21 mA |
|
|
| Accuracy: 0.05% of full scale |
|
|
| Temperature Stability: 0.01% F.S./°C |
|
|
| Load Resistance: 0 to 1000 ohms |
|
|
|
| |
Alarm Outputs | One SPDT Electromechanical relay. A second alarm is available if the second control relay |
| |
(Optional) | is not used for control purposes or when the Dual Relay Option is used. |
| |
|
| Up to four setpoints are independently set as high or low alarm, two for each relay. Setpoint |
|
|
| can be on any Input, Process Variable, Deviation, Manual Mode, Failsafe, PV Rate, RSP |
|
|
| Mode, Communication Shed, or Output. A single adjustable hysteresis of 0.0 to 100.0% is |
|
|
| provided. The alarm can also be set as an ON or OFF event at the beginning of a Setpoint |
|
|
| ramp/soak segment. |
|
|
| Alarm Relay Contacts Rating: Resistive Load: 5 amps at 120 Vac or 240 Vac or 30 Vdc |
|
|
|
| |
Isolation (Functional) | Analog Inputs: are isolated from all other circuits at 850Vdc for 2 seconds, but not from each |
| |
|
| other. |
|
|
| Analog Outputs: are isolated from all other circuits at 850Vdc for 2 seconds. |
|
|
| AC Power: is electrically isolated from all other inputs and outputs to withstand a HIPOT |
|
|
| potential of 1900Vdc for 2 seconds per Annex K of |
|
|
| Relay Contacts: with a working voltage of 115/230 Vac, are isolated from each other and all |
|
|
| other circuits at 345Vdc for 2 seconds. |
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 9 |