Modbus Read, Write and Override Parameters plus Exception Codes
10.7.2SP Ramp/Rate/Program
Table
| Table | |||||
Parameter | Register | Data | Access |
| Data Range or | |
Description | Address | Type |
|
| Enumerated Selection | |
| Hex | Decimal |
|
|
|
|
|
|
|
|
|
|
|
SP Ramp | 0096 | 150 | INT | R/W | 0 | = Disabled |
|
|
|
|
| 1 | = Enabled |
Single SP Ramp | 19 | 25 | FP | R/W | 0 to 255 (minutes) | |
Time |
|
|
|
|
|
|
|
|
|
|
|
| |
Final Ramp SP | 001A | 026 | FP | R/W | PV Range in Engineering | |
Value |
|
|
|
|
| Units |
|
|
|
|
|
|
|
SP Rate | F0 | 240 | INT | R/W | 0 | = Disabled |
|
|
|
|
| 1 | = Enabled |
Rate Up (EU/HR) | 006C | 108 | FP | R/W | 0 to 9999 | |
|
|
|
|
|
| |
Rate Down | 006D | 109 | FP | R/W | 0 to 9999 | |
(EU/HR) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Setpoint | 00B2 | 178 | INT | R/W | 0 | = Disabled |
Program |
|
|
|
| 1 | = Enabled |
|
|
|
|
|
| |
Start Segment # | 58 | 88 | FP | R/W | 1 to 12 | |
|
|
|
|
|
|
|
End Segment | 00B0 | 176 | INT | R/W | 0 | = Soak 2 |
#(Soak) |
|
|
|
| 1 | = Soak 4 |
|
|
|
|
| 2 | = Soak 6 |
|
|
|
|
| 3 | = Soak 8 |
|
|
|
|
| 4 | = Soak 10 |
|
|
|
|
| 5 | = Soak 12 |
Engineering Units | 00B6 | 182 | INT | R/W | 0 | = HRS:MIN |
or Ramp |
|
|
|
| 1 = Degrees/Minute | |
Segments |
|
|
|
| 2 = EU/Hour | |
Program Recycles | 59 | 89 | FP | R/W | 0 to 100 | |
|
|
|
|
|
| |
Guaranteed Soak | 0057 | 087 | FP | R/W | 0 to 99.9 (0 = no soak) | |
Deviation |
|
|
|
|
|
|
|
|
|
|
|
|
|
Program End | 00B5 | 181 | INT | R/W | 0 | = Disable SP Program |
State |
|
|
|
| 1 | = Hold at Program End |
|
|
|
|
|
|
|
198 | UDC2500 Universal Digital Controller Product Manual | 4/07 |