Modbus Read, Write and Override Parameters plus Exception Codes

10.7.2SP Ramp/Rate/Program

Table 10-10lists all the register addresses and ranges or selections for the function parameters in Set-up Group Setpoint Ramp/Rate.

 

Table 10-10 Set-up Group – Setpoint Ramp/Rate

Parameter

Register

Data

Access

 

Data Range or

Description

Address

Type

 

 

Enumerated Selection

 

Hex

Decimal

 

 

 

 

 

 

 

 

 

 

 

SP Ramp

0096

150

INT

R/W

0

= Disabled

 

 

 

 

 

1

= Enabled

Single SP Ramp

19

25

FP

R/W

0 to 255 (minutes)

Time

 

 

 

 

 

 

 

 

 

 

 

 

Final Ramp SP

001A

026

FP

R/W

PV Range in Engineering

Value

 

 

 

 

 

Units

 

 

 

 

 

 

 

SP Rate

F0

240

INT

R/W

0

= Disabled

 

 

 

 

 

1

= Enabled

Rate Up (EU/HR)

006C

108

FP

R/W

0 to 9999

 

 

 

 

 

 

Rate Down

006D

109

FP

R/W

0 to 9999

(EU/HR)

 

 

 

 

 

 

 

 

 

 

 

 

 

Setpoint

00B2

178

INT

R/W

0

= Disabled

Program

 

 

 

 

1

= Enabled

 

 

 

 

 

 

Start Segment #

58

88

FP

R/W

1 to 12

 

 

 

 

 

 

 

End Segment

00B0

176

INT

R/W

0

= Soak 2

#(Soak)

 

 

 

 

1

= Soak 4

 

 

 

 

 

2

= Soak 6

 

 

 

 

 

3

= Soak 8

 

 

 

 

 

4

= Soak 10

 

 

 

 

 

5

= Soak 12

Engineering Units

00B6

182

INT

R/W

0

= HRS:MIN

or Ramp

 

 

 

 

1 = Degrees/Minute

Segments

 

 

 

 

2 = EU/Hour

Program Recycles

59

89

FP

R/W

0 to 100

 

 

 

 

 

 

Guaranteed Soak

0057

087

FP

R/W

0 to 99.9 (0 = no soak)

Deviation

 

 

 

 

 

 

 

 

 

 

 

 

 

Program End

00B5

181

INT

R/W

0

= Disable SP Program

State

 

 

 

 

1

= Hold at Program End

 

 

 

 

 

 

 

198

UDC2500 Universal Digital Controller Product Manual

4/07