Configuration
Function Prompt | Selection or Range of Setting | Parameter | ||
Lower Display | Upper Display | Definition | ||
English | Numeric | English | Numeric |
|
| Code |
| Code |
|
FSMODE | 817 |
|
| FAILSAFE MODE |
|
| No L | 0 | NON |
|
|
|
| mode that was being used (automatic or |
|
|
|
| manual); output goes to failsafe value. |
|
|
|
| (NOTE 1, NOTE 2) |
|
| LACH | 1 | |
|
|
|
| mode; output goes to failsafe value. (NOTE |
|
|
|
| 2) |
|
|
|
|
|
PBorGN | 818 |
|
| PROPORTIONAL BAND |
|
|
|
| one of the following for the Proportional (P) |
|
|
|
| term of the PID algorithm: |
|
| GAIN | 0 | GAIN selects the unitless term of gain for the |
|
|
|
| P term of the PID algorithm. |
|
|
|
| Where: GAIN = 100 % FS |
|
|
|
| PB% |
|
| PB | 1 | PROPORTIONAL BAND selects units of |
|
|
|
| percent proportional band for the P term of |
|
|
|
| the PID algorithm. |
|
|
|
| Where: PB % = 100 % FS |
|
|
|
| GAIN |
MINRPM | 819 |
|
| RESET |
|
|
|
| repeat or repeats per minute for the I term of |
|
|
|
| the PID algorithm. |
|
|
|
| 20 Repeats per Minute = 0.05 Minutes per |
|
|
|
| Repeat. |
|
| MIN | 0 | MINUTES PER |
|
|
|
| between each repeat of the proportional |
|
|
|
| action by reset. |
|
| RPM | 1 | REPEATS PER |
|
|
|
| times per minute that the proportional action |
|
|
|
| is repeated by reset. |
|
|
|
|
|
NOTE 1: Does not apply to Three Position Step Control.
NOTE 2: If controller is in Manual upon failure, output will maintain its value at time of failure.
NOTE 3: These selections appear when the Control Algorithm is selected for 3PSTEP.
NOTE 4: The local setpoint will automatically adjust itself to be within the setpoint limit range. For example, if SP = 1500 and the SP HiLIM is changed to 1200, the new local setpoint will be 1200.
NOTE 5: Reset limits and Dropoff are not displayed when Three Position Step Control is configured.
66 | UDC2500 Universal Digital Controller Product Manual | 4/07 |