Configuration

Function Prompt

Selection or Range of Setting

Parameter

Lower Display

Upper Display

Definition

English

Numeric

English

Numeric

 

 

Code

 

Code

 

FSMODE

817

 

 

FAILSAFE MODE

 

 

No L

0

NON LATCHING—Controller stays in last

 

 

 

 

mode that was being used (automatic or

 

 

 

 

manual); output goes to failsafe value.

 

 

 

 

(NOTE 1, NOTE 2)

 

 

LACH

1

LATCHING—Controller goes to manual

 

 

 

 

mode; output goes to failsafe value. (NOTE

 

 

 

 

2)

 

 

 

 

 

PBorGN

818

 

 

PROPORTIONAL BAND UNITS—Select

 

 

 

 

one of the following for the Proportional (P)

 

 

 

 

term of the PID algorithm:

 

 

GAIN

0

GAIN selects the unitless term of gain for the

 

 

 

 

P term of the PID algorithm.

 

 

 

 

Where: GAIN = 100 % FS

 

 

 

 

PB%

 

 

PB

1

PROPORTIONAL BAND selects units of

 

 

 

 

percent proportional band for the P term of

 

 

 

 

the PID algorithm.

 

 

 

 

Where: PB % = 100 % FS

 

 

 

 

GAIN

MINRPM

819

 

 

RESET UNITS—Selects units of minutes per

 

 

 

 

repeat or repeats per minute for the I term of

 

 

 

 

the PID algorithm.

 

 

 

 

20 Repeats per Minute = 0.05 Minutes per

 

 

 

 

Repeat.

 

 

MIN

0

MINUTES PER REPEAT—The time

 

 

 

 

between each repeat of the proportional

 

 

 

 

action by reset.

 

 

RPM

1

REPEATS PER MINUTE—The number of

 

 

 

 

times per minute that the proportional action

 

 

 

 

is repeated by reset.

 

 

 

 

 

NOTE 1: Does not apply to Three Position Step Control.

NOTE 2: If controller is in Manual upon failure, output will maintain its value at time of failure.

NOTE 3: These selections appear when the Control Algorithm is selected for 3PSTEP.

NOTE 4: The local setpoint will automatically adjust itself to be within the setpoint limit range. For example, if SP = 1500 and the SP HiLIM is changed to 1200, the new local setpoint will be 1200.

NOTE 5: Reset limits and Dropoff are not displayed when Three Position Step Control is configured.

66

UDC2500 Universal Digital Controller Product Manual

4/07

Page 80
Image 80
Honeywell UDC2500 manual Fsmode, Failsafe Mode, Minrpm