Honeywell UDC2500 manual Input 00AB 171

Models: UDC2500

1 243
Download 243 pages 28.29 Kb
Page 222
Image 222

Modbus Read, Write and Override Parameters plus Exception Codes

Parameter

Register

Data

Access

 

 

Data Range or

Description

Address

Type

 

 

 

Enumerated Selection

 

 

 

 

 

 

 

 

 

Hex

Decimal

 

 

 

 

 

 

 

 

 

 

 

 

 

Input 2

00AB

171

INT

R/W

0 = B TC

Transmitter

 

 

 

 

1

= E TC H

Characterization

 

 

 

 

2

= E TC L

 

 

 

 

 

3

= J TC H

 

 

 

 

 

4

= J TC M

 

 

 

 

 

5

= J TC L

 

 

 

 

 

6

= K TC H

 

 

 

 

 

7

= K TC M

 

 

 

 

 

8

= K TC L

 

 

 

 

 

9

= NNM H

 

 

 

 

 

10

= NNM L

 

 

 

 

 

11

= Nicrosil H TC

 

 

 

 

 

12

= Nicrosil L TC

 

 

 

 

 

13

= R TC

 

 

 

 

 

14

= S TC

 

 

 

 

 

15

= T TC H

 

 

 

 

 

16

= T TC L

 

 

 

 

 

17

= W TC H

 

 

 

 

 

18

= W TC L

 

 

 

 

 

19

= 100 PT RTD

 

 

 

 

 

20

= 100 PT LO RTD

 

 

 

 

 

21

= 200 PT RTD

 

 

 

 

 

22

= 500 PT RTD

 

 

 

 

 

23

= Radiamatic RH

 

 

 

 

 

24

= Radiamatic RI

 

 

 

 

 

25

= Linear

 

 

 

 

 

26

= Square Root

 

 

 

 

 

 

Input 2 High

0023

035

FP

R/W

–999. to 9999. Engineering

Range Value

 

 

 

 

Units

 

 

 

 

 

 

Input 2 Low

0024

036

FP

R/W

–999 to 9999. Engineering

Range Value

 

 

 

 

Units

 

 

 

 

 

 

Input 2 Ratio

0025

037

FP

R/W

–20.00 to 20.00

 

 

 

 

 

 

Input 2 Bias

0026

038

FP

R/W

–999 to 9999. Engineering

 

 

 

 

 

Units

 

 

 

 

 

 

Input 2 Filter

002B

043

FP

R/W

0 to 120 seconds

 

 

 

 

 

 

 

 

208