Software Version Number, 160
Solid State Relay Output, 25
SP Ramp Set Up Group, 39
SP Tuning, 43
Specifications, 8
Spprog, 41
Sprate, 40
Start Segment Number, 119
Start Up Procedure For Operation, 99
Station Address, 73
Status Data, 129
Status Tests, 161
Stray Rejection, 8
Suppression Devices, 18
Switch Between Two Sets Via Keyboard, 112
Switching Between Setpoints, 102
T
Temperature Units, 82
Test Failures, 161
Thermocouple Inputs Using A Thermocouple
Source, 141
Thermocouple Inputs Using An Ice Bath, 140
Three Position Step, 48
Three Position Step Control Algorithm, 113
Three Position Step Control Connections, 28
Three Position Step Control Output Failure, 167
Time Current Duplex, 52
Time Duplex, 52
Time Proportional Output, 51
Time Proportional Output Failure, 168
Time Remaining, 103
Time Simplex, 51
Timer, 102
Timer, 49
Transmitter Characterization, 56
Transmitter Power For
Troubleshooting Aids, 159
Troubleshooting Procedures, 165
Troubleshooting/Service, 158
Tune, 44, 104
Tune For Duplex (Heat/Cool), 105
Tuning, 35
Tuning Indicators, 104
Tuning Parameter Sets, 61
Tuning Set Up Group, 35
Two Sets Of Tuning Constants, 110
TX Delay, 74
U
Universal Output Functionality And Restrictions, 20
V
Voltage And Resistance Equivalents For 0% And
100% Range Values, 137, 139
W, X, Y, Z
Weigh, 10
Wiring, 17
Wiring Bundling, 18
Wiring Connections For 1 To 5 Volt Input – Input 2, 147
Wiring Connections For 4 To 20 Ma Input – Input 2, 146
Wiring Connections For Calibrating Auxiliary Output, 154
Wiring Connections For Calibrating Current Output, 152
Wiring Connections For Radiamatic, Milliampere, Millivolts, Or Volts (Except 0 To 10 Volts), 142, 143
Wiring Connections For Rtd (Resistance Thermometer Device), 141
Wiring Diagrams, 19 Wiring The Controller, 21 Worksheet, 118
4/07 | UDC2500 Universal Digital Controller Product Manual | 225 |